Service diagnosis
45
Domestic air conditioner
10.3.11 Loss of synchronism detection
Inverter side current detection is abnormal
Outdoor Display
ƵƾƵ?)
LED1 flash 18 times
ƵƾƵ?)
LED1 flash 19 times
Method of The position of the compressor rotor can not detected normally
Malfunction
Detection
Malfunction when the wiring of compressor is wrong or the connection is poor;
Decision or the compressor is damaged
Conditions
Supposed
Ƶ
Faulty The wiring of compressor
Causes
Ƶ
Faulty compressor
Ƶ
Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller, check whether
the compressor can start up
1. The wiring of compressor is incorrect
or the connection is poor;
2. The compressor is damaged
At first, the compressor start up ,soon the
compressor stopped with the LED1 on the
outdoor PCB blinks
˄
1Hz
˅
19/18 times
IPM Module is damaged and needs
replacing.
the Malfunctions exist also, the
compressor is damaged replace a
new one
YES
NO
YES
Malfunction unsolved
Maybe there is some disturbance
Summary of Contents for GES-NX2G25OUT
Page 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 ...
Page 39: ...Service diagnosis 37 Domestic air conditioner ...
Page 61: ...Removal Procedure 1 Removal of Outdoor Panel ...
Page 62: ...Removal Procedure n o i t i d n o C r i A c i t s e m o D 2 ...
Page 63: ...4 Removal Procedure 3 Domestic Air Condition ...
Page 64: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...
Page 65: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...
Page 66: ...Removal Procedure 4 Removal of Fan Motor Brcked and Partition ...
Page 67: ...Removal Procedure 7 Domestic Air Condition ...
Page 68: ...Removal Procedure 5 Removal of Compressor and Heat Exchanger ...