25
English
All of the above information may be changed without notice.
Installation data
Model
GE AIR Z09
GE AIR Z12
GE AIR Z17
GE AIR Z21
Heating
yes
yes
yes
yes
Power supply connected to
indoor unit
indoor unit
outdoor unit
outdoor unit
Voltage (V) / Frequency (Hz)
220-240 / 50
220-240 / 50
220-240 / 50
220-240 / 50
Refrigerant and charge
R410a 1.2kg
R410a 1.27kg
R410a 1.6kg
R410a 2.4kg
Refrigerant per extra meter of pipe (g)
20
20
20
20
Connection pipe diameter - liquid (inch)
1/4"
1/4"
1/4"
3/8”
Connection pipe diameter - gas (inch)
1/2”
1/2”
1/2”
5/8”
Connection pipes - maximum length (m)
10
10
25
25
Connection pipes - maximum height (m)
5
5
10
10
Climatic rating
T1
T1
T1
T1
Net weight - indoor unit (kg)
11
11
13
13
Unit dimensions - indoor unit (mm) - wxhxd
830x285x189
830x285x189
1020x319x234
1020x319x234
Net weight - outdoor unit (kg)
40
40
52
64
Unit dimensions - outdoor unit (mm) - wxhxd
848x540x320
848x540x320
846x685x300
950x840x420