GE Multilin
G60 Generator Protection System
B-29
APPENDIX B
B.4 MEMORY MAPPING
B
5F89
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F8A
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F8B
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Stator Differential (Read/Write Grouped Setting)
6470
Stator Differential Function
0 to 1
---
1
F102
0 (Disabled)
6471
Stator Differential Pickup
0.05 to 1
pu
0.001
F001
100
6472
Stator Differential Slope 1
1 to 100
%
1
F001
10
6473
Stator Differential Slope 2
1 to 100
%
1
F001
80
6474
Stator Differential Break 1
1 to 1.5
pu
0.01
F001
115
6475
Stator Differential Break 2
1.5 to 30
pu
0.01
F001
800
6476
Stator Differential Block
0 to 65535
---
1
F300
0
6477
Stator Differential Targets
0 to 2
---
1
F109
0 (Self-reset)
6478
Stator Differential Events
0 to 1
---
1
F102
0 (Disabled)
6479
Stator Differential Line End Source
0 to 5
---
1
F167
0 (SRC 1)
647A
Stator Differential Neutral End Source
0 to 5
---
1
F167
0 (SRC 1)
Negative Sequence Overvoltage (Read/Write Grouped Setting)
64A0
Negative Sequence Overvoltage Function
0 to 1
---
1
F102
0 (Disabled)
64A1
Negative Sequence Overvoltage Source
0 to 5
---
1
F167
0 (SRC 1)
64A2
Negative Sequence Overvoltage Pickup
0 to 1.25
pu
0.001
F001
300
64A3
Negative Sequence Overvoltage Pickup Delay
0 to 600
s
0.01
F001
50
64A4
Negative Sequence Overvoltage Reset Delay
0 to 600
s
0.01
F001
50
64A5
Negative Sequence Overvoltage Block
0 to 65535
---
1
F300
0
64A6
Negative Sequence Overvoltage Target
0 to 2
---
1
F109
0 (Self-reset)
64A7
Negative Sequence Overvoltage Events
0 to 1
---
1
F102
0 (Disabled)
Overfrequency (Read/Write Setting) (4 modules)
64D0
Overfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
64D1
Overfrequency 1 Block
0 to 65535
---
1
F300
0
64D2
Overfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
64D3
Overfrequency 1 Pickup
20 to 65
Hz
0.01
F001
6050
64D4
Overfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
500
64D5
Overfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
500
64D6
Overfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
64D7
Overfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
64D8
Reserved (4 items)
0 to 1
---
1
F001
0
64DC
...Repeated for Overfrequency 2
64E8
...Repeated for Overfrequency 3
64F4
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
0 to 1
---
1
F102
0 (Disabled)
65C1
Power Swing Detect Source
0 to 5
---
1
F167
0 (SRC 1)
65C2
Power Swing Detect Mode
0 to 1
---
1
F513
0 (Two Step)
65C3
Power Swing Detect Supervision
0.05 to 30
pu
0.001
F001
600
65C4
Power Swing Detect Forward Reach
0.1 to 500
ohms
0.01
F001
5000
65C5
Power Swing Detect Forward RCA
40 to 90
degrees
1
F001
75
65C6
Power Swing Detect Reverse Reach
0.1 to 500
ohms
0.01
F001
5000
65C7
Power Swing Detect Reverse RCA
40 to 90
degrees
1
F001
75
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...