Installation Instructions

ELECTRICAL CONNECTIONS

You must use a 3-wire, single-phase A.C.
208Y/120 Volt or 240/120 Volt, 60 hertz
electrical system.

If the electrical service provided does not
meet the above specifications, have a
licensed electrician install an approved outlet.

Use only a 3-conductor or a 4-conductor 
UL-listed range cord. These cords may be
provided with ring terminals on wire and 
a strain relief device.

A range cord rated at 40 amps with 125/250
minimum volt range is required. A 50 amp
range cord is not recommended but if used, 
it should be marked for use with nominal 
1

3

8

diameter connection openings. Care

should be taken to center the cable and 
strain relief within the knockout hole to keep
the edge from damaging the cable.

• 

Because range terminals are not accessible
after range is in position, flexible service
conduit or cord must be used.

NOTE: 

If conduit is being used, go to Step 3D

and then to Step 6 or 7.

• 

On some models, a filter capacitor may be
connected between the black and white
leads on the junction block.

ALL NEW CONSTRUCTIONS,
MOBILE HOMES AND
INSTALLATIONS WHERE 
LOCAL CODES DO NOT 
ALLOW GROUNDING 
THROUGH NEUTRAL, 
REQUIRE A 4-CONDUCTOR 
UL-LISTED RANGE CORD.

ELECTRICAL REQUIREMENTS

CAUTION: 

For personal safety,

do not use an extension cord with this
appliance. Remove house fuse or open circuit
breaker before beginning installation.

This appliance must be supplied with the
proper voltage and frequency, and connected
to an individual properly grounded branch
circuit, protected by a circuit breaker or fuse
having amperage appropriate for the wattage
specified on the rating plate. The rating plate
is located above the storage drawer on the
oven frame or on the side of the drawer
frame.

We recommend you have the electrical wiring
and hookup of your range connected by a
qualified electrician. After installation, have
the electrician show you where your main
range disconnect is located.

Check with your local utilities for electrical
codes which apply in your area. Failure to
wire your oven according to governing codes
could result in a hazardous condition. If there
are no local codes, your range must be wired
and fused to meet the requirements of the
National Electrical Code, ANSI/NFPA No. 70–
Latest Edition. You can get a copy by writing:

National Fire Protection Association

Batterymarch Park

Quincy, MA  02269

Effective January 1, 1996, the National
Electrical Code requires that new construction
(not existing) utilize a 4-conductor connection
to an electric range.

When installing an electric range in new
construction, follow Steps 3 and 5 for 4-wire
connection.

Location of
model rating
plate

Summary of Contents for Free-Standing Ranges

Page 1: ...e beginning the installation switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device such as a tag to the service panel ANTI TIP DEVICE WARNING To reduce the risk of tipping the appliance must be secured by properly installed Anti ...

Page 2: ...st be no deeper than 13 Be sure your appliance is properly installed and grounded by a qualified technician Make sure the cabinets and wall coverings around the range can withstand the temperatures up to 200 F generated by the range 2 Installation Instructions PREPARE TO INSTALL THE RANGE MATERIALS YOU MAY NEED Anchor Sleeves Lag Bolts For Anti Tip Bracket Mounted on Concrete Floors Only 3 Wire Co...

Page 3: ...OVE THE COOKTOP Make sure the wall covering countertop flooring and cabinets around the range can withstand the heat up to 200 F generated by the range Allow 30 minimum clearance between surface units and bottom of unprotected wood or metal cabinet and 15 minimum between countertop and adjacent cabinet bottom Recommended spacing to heat sensitive surfaces 2 21 2 21 2 71 2 25 36 30 Acceptable elect...

Page 4: ...MENTS CAUTION For personal safety do not use an extension cord with this appliance Remove house fuse or open circuit breaker before beginning installation This appliance must be supplied with the proper voltage and frequency and connected to an individual properly grounded branch circuit protected by a circuit breaker or fuse having amperage appropriate for the wattage specified on the rating plat...

Page 5: ...strain relief they can be removed for better fit NOTE Do not install the power cord without a strain relief The strain relief bracket should be installed before reinstalling the rear range wiring cover Skip to Step 4 or 5 C Wire cover 5 screws to remove wire cover Knockout ring in bracket Knockout ring removed Power cord Strain relief Terminal block Bracket Retaining tabs Back of range Terminal bl...

Page 6: ...tral is connected to the center lower position of the terminal block Tighten screws securely into the terminal block Skip to Step 8 and proceed with the installation E D C B A 5 3 WIRE POWER CORD INSTALLATION WARNING The neutral or ground wire of the power cord must be connected to the neutral terminal located in the center of the terminal block The power leads must be connected to the lower left ...

Page 7: ...local codes Skip to Step 8 and proceed with the installation B A 6 4 WIRE CONDUIT INSTALLATION Loosen the three lower terminal screws from the terminal block Remove the ground screw and ground plate and retain them Cut and discard the ground strap DO NOT DISCARD ANY SCREWS Insert the ground bare wire tip between the range frame and the ground plate removed earlier and secure it in place with the g...

Page 8: ... liquids or from the range itself 9 Typical installation of anti tip bracket attachment to wall Bracket Screw must enter wood or metal Wall plate REPLACE THE WIRE COVER Replace the wire cover on the range back by sliding its left edge under the retaining tabs and replacing the five screws removed earlier Make sure that no wires are pinched between the cover and the range back 8 REMOVE STORAGE DRAW...

Page 9: ...e door and drawer are parallel to each other and that both operate smoothly If they do not see the Owner s Manual for proper replacement Check to make sure that the rear leveling leg is fully inserted into the Anti Tip bracket and that the bracket is securely installed 14 OPERATION CHECKLIST Turn on one of the surface units to observe that the element glows within 60 seconds Turn the unit off when...

Page 10: ...10 Notes ...

Page 11: ...11 Notes ...

Page 12: ...12 Printed in the United States ...

Reviews: