GE Multilin
F60 Feeder Protection System
3-23
3 HARDWARE
3.2 WIRING
3
3.2.7 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the F60 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at
19200 bps
.
Figure 3–25: RS232 FACEPLATE PORT CONNECTION
3.2.8 CPU COMMUNICATION PORTS
a) OPTIONS
In addition to the faceplate RS232 port, the F60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPE
COM1
COM2
9E
RS485
RS485
9G
10Base-F and 10Base-T
RS485
9H
Redundant 10Base-F
RS485
9J
100Base-FX
RS485
9K
Redundant 100Base-FX
RS485
9L
100Base-FX
RS485
9M
Redundant 100Base-FX
RS485
9N
10/100Base-T
RS485
9P
100Base-FX
RS485
9R
Redundant 100Base-FX
RS485
9S
Ethernet switch module with two 10/100Base-T and four 100Base-FX ports
RS485
NOTE
NOTE
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...