B-56
F60 Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
C6C8
...Repeated for Contact Output 55
C6D4
...Repeated for Contact Output 56
C6E0
...Repeated for Contact Output 57
C6EC
...Repeated for Contact Output 58
C6F8
...Repeated for Contact Output 59
C704
...Repeated for Contact Output 60
C710
...Repeated for Contact Output 61
C71C
...Repeated for Contact Output 62
C728
...Repeated for Contact Output 63
C734
...Repeated for Contact Output 64
Reset (Read/Write Setting)
C750
FlexLogic™ operand which initiates a reset
0 to 65535
---
1
F300
0
Control Pushbuttons (Read/Write Setting) (7 modules)
C760
Control Pushbutton 1 Function
0 to 1
---
1
F102
0 (Disabled)
C761
Control Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
C762
...Repeated for Control Pushbutton 2
C764
...Repeated for Control Pushbutton 3
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
C770
Clear Fault Reports operand
0 to 65535
---
1
F300
0
C772
Clear Event Records operand
0 to 65535
---
1
F300
0
C773
Clear Oscillography operand
0 to 65535
---
1
F300
0
C774
Clear Data Logger operand
0 to 65535
---
1
F300
0
C775
Clear Breaker 1 Arcing Current operand
0 to 65535
---
1
F300
0
C776
Clear Breaker 2 Arcing Current operand
0 to 65535
---
1
F300
0
C77B
Clear Demand operand
0 to 65535
---
1
F300
0
C77D
Clear Energy operand
0 to 65535
---
1
F300
0
C77E
Clear Hi-Z Records operand
0 to 65535
---
1
F300
0
C77F
Clear Unauthorized Access operand
0 to 65535
---
1
F300
0
C781
Clear Platform Direct Input/Output Statistics operand
0 to 65535
---
1
F300
0
C782
Reserved (13 items)
---
---
---
F001
0
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input
x
State (96 items)
0 to 2
---
1
F144
0 (Disabled)
C800
Force Contact Output
x
State (64 items)
0 to 3
---
1
F131
0 (Disabled)
Direct Inputs/Outputs (Read/Write Setting)
C880
Direct Device ID
1 to 16
---
1
F001
1
C881
Direct I/O Channel 1 Ring Configuration Function
0 to 1
---
1
F126
0 (No)
C882
Platform Direct I/O Data Rate
64 to 128
kbps
64
F001
64
C883
Direct I/O Channel 2 Ring Configuration Function
0 to 1
---
1
F126
0 (No)
C884
Platform Direct I/O Crossover Function
0 to 1
---
1
F102
0 (Disabled)
Direct input/output commands (Read/Write Command)
C888
Direct input/output clear counters command
0 to 1
---
1
F126
0 (No)
Direct inputs (Read/Write Setting) (96 modules)
C890
Direct Input 1 Device Number
0 to 16
---
1
F001
0
C891
Direct Input 1 Number
0 to 96
---
1
F001
0
C892
Direct Input 1 Default State
0 to 3
---
1
F086
0 (Off)
C893
Direct Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
C894
...Repeated for Direct Input 2
C898
...Repeated for Direct Input 3
C89C
...Repeated for Direct Input 4
C8A0
...Repeated for Direct Input 5
Table B–9: MODBUS MEMORY MAP (Sheet 48 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...