GE Multilin
F60 Feeder Protection System
B-43
APPENDIX B
B.4 MEMORY MAPPING
B
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector switch actual values (read only)
A210
Selector switch 1 position
1 to 7
---
1
F001
0
A211
Selector switch 2 position
1 to 7
---
1
F001
1
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 65535
---
1
F300
0
A284
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A285
Selector 1 Acknowledge
0 to 65535
---
1
F300
0
A286
Selector 1 Bit0
0 to 65535
---
1
F300
0
A287
Selector 1 Bit1
0 to 65535
---
1
F300
0
A288
Selector 1 Bit2
0 to 65535
---
1
F300
0
A289
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28A
Selector 1 Bit Acknowledge
0 to 65535
---
1
F300
0
A28B
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A28C
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A28D
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A28E
Reserved (10 items)
---
---
1
F001
0
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 65535
---
1
F300
0
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F300
0
Flexcurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset Dominant)
A702
Non-Volatile Latch 1 Set
0 to 65535
---
1
F300
0
A703
Non-Volatile Latch 1 Reset
0 to 65535
---
1
F300
0
A704
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A705
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A706
Reserved (4 items)
---
---
---
F001
0
A70A
...Repeated for Non-Volatile Latch 2
A714
...Repeated for Non-Volatile Latch 3
A71E
...Repeated for Non-Volatile Latch 4
A728
...Repeated for Non-Volatile Latch 5
A732
...Repeated for Non-Volatile Latch 6
A73C
...Repeated for Non-Volatile Latch 7
A746
...Repeated for Non-Volatile Latch 8
A750
...Repeated for Non-Volatile Latch 9
A75A
...Repeated for Non-Volatile Latch 10
A764
...Repeated for Non-Volatile Latch 11
A76E
...Repeated for Non-Volatile Latch 12
A778
...Repeated for Non-Volatile Latch 13
A782
...Repeated for Non-Volatile Latch 14
A78C
...Repeated for Non-Volatile Latch 15
A796
...Repeated for Non-Volatile Latch 16
Table B–9: MODBUS MEMORY MAP (Sheet 35 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...