5-184
F60 Feeder Protection System
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
5.6.11 MONITORING ELEMENTS
a) MAIN MENU
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
MONITORING ELEMENTS
b) HIGH IMPEDANCE FAULT DETECTION
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
MONITORING ELEMENTS
Ö
HI-Z
MONITORING
ELEMENTS
HI-Z
MESSAGE
BREAKER 1
ARCING CURRENT
MESSAGE
BREAKER 2
ARCING CURRENT
MESSAGE
BREAKER
FLASHOVER 1
MESSAGE
BREAKER
FLASHOVER 2
MESSAGE
BREAKER RESTRIKE 1
MESSAGE
INCIPIENT FAULT 1
MESSAGE
INCIPIENT FAULT 2
MESSAGE
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
HI-Z
HI-Z FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
HI-Z SOURCE:
SRC 1
Range: SRC 1, SRC 2
MESSAGE
HI-Z ARCING
SENSITIVITY: 5
Range: 1 to 10 in steps of 1
MESSAGE
HI-Z ARCING DET SOE
RESET TIME: 0.0 s
Range: 0.0 to 6000.0 s in steps of 0.1
MESSAGE
HI-Z PHASE EVENT
COUNT: 30
Range: 10 to 250 in steps of 1
MESSAGE
HI-Z GROUND EVENT
COUNT: 30
Range: 10 to 500 in steps of 1
MESSAGE
HI-Z EVENT COUNT
TIME: 15
min
Range: 5 to 180 min. in steps of 1
MESSAGE
HI-Z OC PROTECTION
COORD TIMEOUT: 15 s
Range: 10 to 200 s in steps of 1
MESSAGE
HI-Z PHASE OC MIN
PICKUP: 1.50
pu
Range: 0.01 to 10.00 pu in steps of 0.01
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...