7.1.1 Virtual inputs
COMMANDS
VIRTUAL INPUTS
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).
7.1.2 Clear records
COMMANDS
CLEAR RECORDS
COMMANDS
VIRTUAL INPUTS
Virt Ip 1
Off
Range: Off, On
Virt Ip 2
Off
Range: Off, On
Virt Ip 64
Off
Range: Off, On
COMMANDS
CLEAR RECORDS
CLEAR FAULT REPORTS?
No
Range: No, Yes
CLEAR EVENT RECORDS?
No
Range: No, Yes
CLEAR OSCILLOGRAPHY?
No
Range: No, Yes
CLEAR DATA LOGGER?
No
Range: No, Yes
CLEAR BREAKER 1
ARCING AMPS? No
Range: No, Yes
CLEAR BREAKER 2
ARCING AMPS? No
Range: No, Yes
CLEAR DEMAND
RECORDS? No
Range: No, Yes
CLEAR ENERGY?
No
Range: No, Yes
CLEAR UNAUTHORIZED
ACCESS? No
Range: No, Yes
CLEAR DIRECT I/O
COUNTERS? No
Range: No, Yes.
Valid only for units with Direct Input/Output module.
CLEAR TELEPROTECT
COUNTERS? No
Range: No, Yes
CLEAR INCIPIENT
FAULT COUNTERS? No
Range: No, Yes
CLEAR IEC61850
XWSI OPCNT
See below
CLEAR IEC61850
XCBR OPCNT
See below
CLEAR ALL RELAY
RECORDS? No
Range: No, Yes