Digital Energy™
g
OPM_LPS_3UI_10K_20K_0US_V010.doc
14/38
Installation Guide
LP 33
/ 10 - 20 kVA
3.3.2
Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind
that
they are subject to auto-discharging process
To avoid permanent damages to the battery, you must observe the following instructions:
•
The storage time without charging the battery depends on the temperature of the storage
ambient.
•
The optimal ambient temperature for the batteries is
68°F
(20°C).
For storage temperature higher than
68°F
(20°C), the storage time will decrease.
•
Each additional
18°F
(10°C) over the nominal temperature of
68°F
(20°C) will decrease the
storage time, without freshening charge, by half.
In case of a
maintenance free battery
, the storage time without charging the
battery
is
approximately:
6 months with storage temperature 68°F (20°C)
3 months with storage temperature 86°F (30°C)
2 months with storage temperature 95°F (35°C)
NOTE !
In case of
battery
storage pay
attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST
SENSITIVE