GE Multilin
C60 Breaker Protection System
6-9
6 ACTUAL VALUES
6.2 STATUS
6
Accuracy is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP
STATE
is the present state of the port’s PTP clock. The PTP clock state is:
•
DISABLED
is the port’s function setting is Disabled,
•
NO SIGNAL
if enabled but no signal from an active master has been found and selected,
•
CALIBRATING
if an active master has been selected but lock is not at present established,
•
SYNCH’D (NO PDELAY)
if the port is synchronized, but the peer delay mechanism is non-operational, and
•
SYNCHRONIZED
if synchronized.
PTP-— IRIG-B DELTA
is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to
IRIG-B time.
6.2.15 DIRECT INPUTS
PATH: ACTUAL VALUES
STATUS
DIRECT INPUTS
The
AVERAGE MSG RETURN TIME
is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The
UNRETURNED MSG COUNT
values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The
CRC FAIL COUNT
values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The
UNRETURNED MSG COUNT
and
CRC FAIL
COUNT
values can be cleared using the
CLEAR DIRECT I/O COUNTERS
command.
The
DIRECT INPUT 1
to
DIRECT INPUT (32)
values represent the state of each direct input.
DIRECT INPUTS
AVG MSG RETURN
TIME CH1: 0 ms
MESSAGE
UNRETURNED MSG
COUNT CH1: 0
MESSAGE
CRC FAIL COUNT
CH1: 0
MESSAGE
AVG MSG RETURN
TIME CH2: 0 ms
MESSAGE
UNRETURNED MSG
COUNT CH2: 0
MESSAGE
CRC FAIL COUNT
CH2: 0
MESSAGE
DIRECT INPUT 1:
On
MESSAGE
DIRECT INPUT 2:
On
↓
MESSAGE
DIRECT INPUT 32:
On
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...