GE Multilin
C60 Breaker Protection System
5-149
5 SETTINGS
5.5 FLEXLOGIC
5
ELEMENT
Breaker flashover
BKR 1 FLSHOVR PKP A
BKR 1 FLSHOVR PKP B
BKR 1 FLSHOVR PKP C
BKR 1 FLSHOVR PKP
BKR 1 FLSHOVR OP A
BKR 1 FLSHOVR OP B
BKR 1 FLSHOVR OP C
BKR 1 FLSHOVR OP
BKR 1 FLSHOVR DPO A
BKR 1 FLSHOVR DPO B
BKR 1 FLSHOVR DPO C
BKR 1 FLSHOVR DPO
Breaker 1 flashover element phase A has picked up
Breaker 1 flashover element phase B has picked up
Breaker 1 flashover element phase C has picked up
Breaker 1 flashover element has picked up
Breaker 1 flashover element phase A has operated
Breaker 1 flashover element phase B has operated
Breaker 1 flashover element phase C has operated
Breaker 1 flashover element has operated
Breaker 1 flashover element phase A has dropped out
Breaker 1 flashover element phase B has dropped out
Breaker 1 flashover element phase C has dropped out
Breaker 1 flashover element has dropped out
BKR 2 FLSHOVR
Same set of operands as shown for BKR 1 FLSHOVR
ELEMENT:
Breaker arcing
BKR ARC 1 OP
BKR ARC 1 DPO
BKR ARC 2 OP
BKR ARC 2 DPO
Breaker arcing current 1 has operated
Breaker arcing current 1 has dropped out
Breaker arcing current 2 has operated
Breaker arcing current 2 has dropped out
BKR ARC 3 to 4
Same set of operands as shown for BKR ARC 1
ELEMENT
Breaker failure
BKR FAIL 1 RETRIPA
BKR FAIL 1 RETRIPB
BKR FAIL 1 RETRIPC
BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
BKR FAIL 1 T2 OP
BKR FAIL 1 T3 OP
BKR FAIL 1 TRIP OP
Breaker failure 1 re-trip phase A (only for 1-pole schemes)
Breaker failure 1 re-trip phase B (only for 1-pole schemes)
Breaker failure 1 re-trip phase C (only for 1-pole schemes)
Breaker failure 1 re-trip 3-phase
Breaker failure 1 timer 1 is operated
Breaker failure 1 timer 2 is operated
Breaker failure 1 timer 3 is operated
Breaker failure 1 trip is operated
BKR FAIL 2
Same set of operands as shown for BKR FAIL 1
ELEMENT
Breaker restrike
BRK RESTRIKE 1 OP
BRK RESTRIKE 1 OP A
BRK RESTRIKE 1 OP B
BRK RESTRIKE 1 OP C
Breaker restrike detected in any phase of the breaker control 1 element
Breaker restrike detected in phase A of the breaker control 1 element
Breaker restrike detected in phase B of the breaker control 1 element
Breaker restrike detected in phase C of the breaker control 1 element
BKR RESTRIKE 2
Same set of operands as shown for BKR RESTRIKE 1
ELEMENT:
Breaker control
BREAKER 1 OFF CMD
BREAKER 1 ON CMD
BREAKER 1
Φ
A BAD ST
BREAKER 1
Φ
A INTERM
BREAKER 1
Φ
A CLSD
BREAKER 1
Φ
A OPEN
BREAKER 1
Φ
B BAD ST
BREAKER 1
Φ
B INTERM
BREAKER 1
Φ
B CLSD
BREAKER 1
Φ
B OPEN
BREAKER 1
Φ
C BAD ST
BREAKER 1
Φ
C INTERM
BREAKER 1
Φ
C CLSD
BREAKER 1
Φ
C OPEN
BREAKER 1 BAD STATUS
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
Breaker 1 open command initiated
Breaker 1 close command initiated
Breaker 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase A is closed
Breaker 1 phase A is open
Breaker 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase B intermediate status is detected (transition from one
position to another)
Breaker 1 phase B is closed
Breaker 1 phase B is open
Breaker 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase C intermediate status is detected (transition from one
position to another)
Breaker 1 phase C is closed
Breaker 1 phase C is open
Breaker 1 bad status is detected on any pole
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
BREAKER 2 to 4
Same set of operands as shown for BREAKER 1
ELEMENT:
Digital counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Digital counter 1 output is ‘more than’ comparison value
Digital counter 1 output is ‘equal to’ comparison value
Digital counter 1 output is ‘less than’ comparison value
Counter 2 to 8
Same set of operands as shown for Counter 1
Table 5–18: C60 FLEXLOGIC OPERANDS (Sheet 2 of 7)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...