GE Multilin
B90 Low Impedance Bus Differential System
6-5
6 ACTUAL VALUES
6.2 STATUS
6
6.2.7 REMOTE DEVICES
a) STATUS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATUS
The present state of the programmed remote devices is shown here. The
ALL REMOTE DEVICES ONLINE
message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATISTICS
REMOTE DEVICE 1
(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
StNum
number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The
SqNum
number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
6.2.8 FLEX STATES
PATH: ACTUAL VALUES
STATUS
FLEX STATES
There are 256 FlexState
TM
bits available. The second line value indicates the state of the given FlexState bit.
REMOTE DEVICES
STATUS
All REMOTE DEVICES
ONLINE: No
Range: Yes, No
MESSAGE
REMOTE DEVICE 1
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 16
STATUS: Offline
Range: Online, Offline
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
FLEX STATES
PARAM 1:
Off
Off
Range: Off, On
MESSAGE
PARAM 2:
Off
Off
Range: Off, On
MESSAGE
PARAM 256: Off
Off
Range: Off, On
Summary of Contents for B90 UR Series
Page 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...