GE Multilin
B90 Low Impedance Bus Differential System
5-11
5 SETTINGS
5.2 PRODUCT SETUP
5
Login: This setting is applicable for
Local Authentication
only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the “Supervisor Role” setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. 20 alphanumeric characters are
acceptable as passwords.The UR device supports five roles. All roles have their corresponding passwords. The Observer
role is the only role that does not require a password.
The roles are defined as follows:
•
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
•
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
•
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
•
Supervisor: This is only an approving role. This role’s authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
•
Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device.
The Factory service role is not available and intended for factory use only.
c) LOCAL PASSWORDS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
CHANGE LOCAL PASSWORDS
The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.
The “login setting” in this menu is similar to the login setting described in
PATH: SETTINGS > PRODUCT SETUP > SECU-
RITY
except for the factory role.
Passwords are stored in text format. No encryption is applied.
Notes:
•
In Local Authentication mode, the Observer role does not have a password associated with it. In Remote Authentica-
tion mode the Observer role requires a password.
•
The default password is “ChangeMe1#”.
•
Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
MESSAGE
SUPERVISORY
MESSAGE
SYSLOG IP ADDRESS:
0.0.0.0
Range: 0.0.0.0, -255.255.255.255
Default: 0.0.0.0
MESSAGE
SYSLOG PORT NUMBER:
514
Range: 1 to 65535
Default: 514
CHANGE LOCAL
PASSWORDS
LOGIN:
None
Range: 20 Alphanumeric Characters
MESSAGE
NEW PASSWORD:
Range: 20 Alphanumeric Characters
MESSAGE
CONFIRM PASSWORD:
Range: 20 Alphanumeric Characters
NOTE
NOTE
Summary of Contents for B90 UR Series
Page 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...