5-26
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE
— This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are in
English.
For Japanese and Chinese, up to 10 characters can be input in a field on the graphical front panel, not 20.
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always
second, and Language is always first.
If the language is changed after entering user-configured names, such as relay names, the strings are not translated. For
example, a relay name is entered in English, the language is changed to Japanese, and the relay name remains in English.
Set the language before changing settings.
The language can be selected also for the front panel in EnerVista under
Maintenance > Change Front Panel
.
The language of the EnerVista software can be changed under
View > Language
.
FLASH MESSAGE TIME
— Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT
— If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY
— To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE
and
SCREEN SAVER WAIT TIME
— These settings are only visible if the B30 has a liquid crystal display
(LCD) and control its backlighting. When the
SCREEN SAVER FEATURE
is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT
followed by the
SCREEN SAVER WAIT TIME
, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL
— This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The B30 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the
CURRENT CUT-OFF LEVEL
setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL
— This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The B30
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
SCREEN SAVER WAIT
TIME: 30 min
Range: 1 to 65535 min. in steps of 1
Visible when an LCD is installed
CURRENT CUT-OFF
LEVEL: 0.020 pu
Range: 0.002 to 0.020 pu in steps of 0.001
VOLTAGE CUT-OFF
LEVEL: 1.0 V
Range: 0.1 to 1.0 V secondary in steps of 0.1
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...