Installation Instructions
Capacity Adjustments Instructions for Connect Series
AUH2436ZGDA Default capacity setting of outdoor unit is 36K, AUH4860ZGDA Default capacity setting of outdoor unit
is 60K. Installer will need to change dip switch to 24k when pairing with a 24 indoor AHU OR dip switch to 48K when pairing
with a 48K indoor AHU. Operation Instruction is below:
1. Dip switch settings must be completed before power on the unit.
2. Capacity dip switch is indicated by the red circle below.
Main control Board
Capacity Dip Switch
Dip Switch Configuration
Model Number
Tonnage
1
2
3
4
AUH2436ZGDA
36k (default)
ON
ON
OFF
OFF
24k
OFF
ON
OFF
OFF
AUH4860ZGDA
60k (default)
ON
ON
OFF
OFF
48k
OFF
ON
OFF
OFF