background image

 

 

 Solver

PROBLEM

AIR CONDITIONER
DOES 

 OPERATE

AIR CONDITIONER

“DOES NOT COOL

AS IT SHOULD”

OPERATING
SOUNDS

WATER 
OUTSIDE

WATER 
INSIDE

WATER IN BASE PAN

(ON OUTDOOR SIDE)

POSSIBLE CAUSE AND REMEDY

● 

Not plugged in. Plug 

may have been bumped loose by vacuum cleaner or furniture.

● 

If plugged in, fuse could have blown or circuit breaker may have been tripped.

● 

Curtains, blinds or furniture blocking front of air conditioner will restrict airflow.

. Thermostat Control may not be set high enough. Also, when Energy Saver Switch

is at SAVE, the temperature in the room will vary more than when it’s at NORMAL.
Turn knob to a higher number. Highest setting should provide maximum cooling.

. Air filter dirty, should be cleaned at least every 30 days. See instructions on page 6.

 Room may have been very hot when air conditioner was first turned on. Allow

time for it to cool down.

. Cold air maybe escaping through open furnace floor registers and cold air returns.

 Ventilation Control maybe set at OPEN, allowing hot outside air to enter room.

● 

Cooling coils have iced up. To melt ice, set the Fan at high speed and the

Thermostat Control to a lower number.

● 

Thermostat click, a metallic sound, maybe heard when compressor cycles on and

off. This is normal.

 Fan cycles on and off with compressor when Energy Saver Switch is at SAVE and

Selector Switch is in cool or heat position. Otherwise, fan runs continuously when
air conditioner is on.

● 

Excess water may overflow in extremely hot and humid weather. This is normal.

● 

Air conditioner must be 

 level or tilted slightly to the outside for proper

water 

. This is normal for a short period in areas with little humidity; normal for a longer

period in very humid areas. Moisture removed from indoor air drains to rear of
cabinet where it is picked up by a fan and thrown against the outdoor condenser coil.

If you need more help.. call, toll free:
GE Answer 
800.626.2000
consumer information service

If You Need Service

 obtain service, see your warranty

on the back page of this book.

We’re proud of our service and
want you to be pleased. If for some

reason you are not happy with the

 you receive, here are three

 to follow for further help.

FIRST, contact the people who
serviced your appliance. Explain

why you are not pleased. In most

FINALLY, if your problem is still

cases, this will solve the problem.

not resolved, write:

NEXT, if you are still not pleased,

Major Appliance

write all the details (including your

Consumer Action Panel

 number) to:

20 North 

 Drive

 Consumer Relations

GE 
Appliance Park
Louisville, Kentucky 40225

Chicago, Illinois 60606

7

Summary of Contents for ANK12D

Page 1: ...ppliance Registration 2 Safety Instructions 2 Care and Cleaning 6 User Maintenance Instructions 6 Condenser Coils 6 Warranty Back Cover Control Settings 4 5 Electrical Requirements 3 Energy Saving Tips 2 Extension Cords 3 Grille and Cabinet 6 GEAmwer CenteP Grounding 3 80 62 2flf10 Heat Cool Models ANK12D mK15D AWK18D GEAppiances ...

Page 2: ...erly installed in accordance with the Installation Instructions before it is used See grounding instructions on page 3 Never unplug yow air conditioner by pulling on the power cord Always grip plug firmly and pull straight out from the receptacle Repair or replace immediately all electric service cords that have become frayed or otherwise damaged Do not use a cord that shows cracks or abrasion dam...

Page 3: ...rom the adapter always hold the adapter with one hand If this is not done the adapter ground terminal is very likely to break with repeated use Should the adapter ground terminal break DO N USE the appliance until a proper ground has again been established personal responsibility and bligation to have it replaced with a properly Whether your air conditioner is a grounded three prong wall outlet 11...

Page 4: ...n HIGH COOL permits cooling with high fan speed operation LOW HEAT permits heating with low fan speed operation MED HEAT permits heating with medium fan speed operation HIGH HEAT permits heating with high fan speed operation THERMOSTAT Thermostat Control When you turn this control to the desired setting the thermostat will automatically control the temperature of the indoor air The higher the numb...

Page 5: ...ou always set the Selector Switch at HIGH COOL in extremely hot weather For air circulation and filtering without cooling or heating Set Selector Switch at FAN ONLY For fan only operation the Energy Saver Switch must be in the NORMAL position For Ventilation Whether controls are set for cooling heating or fan only operation setting Ventilation Control at OPEN lets room air be exhausted to the outs...

Page 6: ...d at least every 30 days or as often as it needs cleaning Front Grille Removal If your air conditioner is mounted flush inside the room or if the window sill extends farther into the room than the chassis it may be necessary to remove the front grille before the filter can be removed To remove the filter To remove the grille Grasp the tab at the bottom left side of the unit and pull downward Clean...

Page 7: ...sor cycles on and off This is normal c Fan cycles on and off with compressor when Energy Saver Switch is at SAVE and Selector Switch is in cool or heat position Otherwise fan runs continuously when air conditioner is on Excess water may overflow in extremely hot and humid weather This is normal Air conditioner must be instiled level or tilted slightly to the outside for proper water disuosal This ...

Page 8: ...E WHAT IS NOT COVERED Service trips to teach you how to use the product Read your Use and Care material If you then have any questions about operating the product please contact your dealer or our Consumer Affairs office at the address below or call toll free GE Answer Cente 800 626 2000 consumer information service Improper installation If you have an installation problem or if the air conditione...

Reviews: