A M P1B1 , A M P1C 2 , A M P1C 3 Com pac t Powe r a nd E ne rg y M ete r
Solid State Output
AMP1 Series meters have one normally open (N.O.) KY Form A
output and one normally closed (N.C.) output.
3
One is dedicated
to energy (Wh), and the other to Alarm. The AMP1B1 also
provides an additional N.O. reactive energy (VARh) contact.
See the Setup section for configuration information.
The solid state pulse outputs are rated for 30 VAC/DC nom.
Maximum load current is 100 mA at 25°C.
1 The over-current protective device must be rated for the
short circuit current at the connection point.
2 All pulse outputs and communication circuits are only intended to be connected to
non-hazardous voltage circuits (SELV or Class 2). Do not connect to hazardous voltages.
3 While the relay used for the Phase Loss contact is Normally Closed (contacts are closed
when the meter is not powered), closure indicates the presence of an alarm; either loss of
phase, when the meter is powered, or loss of power when the meter is not. The contacts
are open when the meter is powered and no phase loss alarm conditions are present.
User Interface Menu Abbreviation Defined
The user can set the display mode to IEC or IEEE notation in the
SETUP menu.
~
=
~
=
≤ 100 mA
≤ 100 mA
≤ 100 mA
~
=
Alarm Energy Output
+ – S
LOAD
LOAD
LOAD
Over-Current Protective
Device
1
(not supplied)
Power Source
2
3-30 VDC
6-30 VAC
(AMP1B1 and AMP1Cx)
(AMP1B1 only)
Power Source
2
3-30 VDC
6-30 VAC
Power Source
2
3-30 VDC
6-30 VAC
Main Menu
IEC
IEEE
Description
D
D
Demand
MAX
M
Maximum Demand
P
W
Present Real Power
Q
VAR
Present Reactive Power
S
VA
Present Apparent Power
A
A
Amps
UAB, UBC, UAC
VAB, VBC, VAC
Voltage Line to Line
V
VLN
Voltage Line to Neutral
PF
PF
Power Factor
U
VLL
Voltage Line to Line
HZ
HZ
Frequency
KSh
KVAh
Accumulated Apparent Energy
KQh
KVARh
Accumulated Reactive Energy
KPh
KWh
Accumulated Real Energy
PLOSS
PLOSS
Phase Loss
LOWPF
LOWPF
Low Power Factor Error
F ERR
F ERR
Frequency Error
I OVR
I OVR
Over Current
V OVR
V OVR
Over Voltage
PULSE
PULSE
kWh Pulse Output Overrun
(configuration error)
_PHASE
_PHASE
Summary Data for 1, 2, or 3
active phases
ALERT
ALERT
Diagnostic Alert Status
INFO
INFO
Unit Information
MODEL
MODEL
Model Number
OS
OS
Operating System
RS
RS
Reset System
SN
SN
Serial Number
RESET
RESET
Reset Data
PASWD
PASWD
Enter Reset or Setup Password
ENERG
ENERG
Reset Energy Accumulators
DEMND
DEMND
Reset Demand Maximums