AKD-20 AR / Entellisys AR Low-voltage Switchgear
DEH-41473
Appendix F. Exhaust Plenum System Details
79
©2016 General Electric. All rights reserved.
Exhaust Plenum T-Section
The exhaust plenum t-sections may be provided in widths of 22, 30, and 38 inches (Figure F.12).
Figure F.12 Exhaust plenum t-section details
Table F.2 Exhaust plenum t-section widths (inches)
Stack Width Dimension “A” Dimension “B” Qty. of “C” Holes Dimension “D”
22
22
20
18
5
30
30
28
22
9
38
38
36
26
13
NOTICE: Use of optional flange clips (Figure F.10) may be
used in lieu of the #12-24 x 7/8 inch hardware. Two flange
clips may be installed on each long exterior flange and one
flange clip may be installed on each short exterior flange.
Use of the optional flange clips will still require the
installation of the 3/8-16 x 1 inch carriage bolts at each
exterior flange corner.