3.15 RS-## Resolver Interface
RS-50 Poles
Range:
Function:
2
*
[2 - 8]
Set the number of poles on the resolver.
The value is stated in the data sheet for resolvers.
RS-51 Input Voltage
Range:
Function:
7 V
*
[2 - 8 V] Set the input voltage to the resolver. The
voltage is stated as RMS value.
The value is stated in the data sheet for
resolvers
RS-52 Input Frequency
Range:
Function:
10 kHz
*
[2 - 15 kHz] Set the input frequency to the resolver.
The value is stated in the data sheet for
resolvers.
RS-53 Transformation Ratio
Range:
Function:
0.5
*
[0.1 - 1.1] Set the transformation ratio for the resolver.
The transformation ration is:
Tratio =
VOut
VIn
The value is stated in the data sheet for
resolvers.
RS-59 Resolver Interface
Activate the OPCRES resolver option when the resolver
parameters are selected.
To avoid damage to resolvers
–
must be adjusted before activating this parameter.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
3.16 Parameter Data Check
3.16.1 Last 10 Changes
Displays a list of the 10 last changes made to the
parameters in the present parameter setup. This allows for
any corrections of the last 10 changes.
3.16.2 Since Factory Settings
Displays a list of all the parameter changes since the
factory settings of the drive or since the last factory restore
of parameters.
3.17 ID-##
Drive
Information
Parameter group related to drive information such as
operating data, hardware configuration and software
version.
3.17.1 ID-0# Operating Data
Parameters to view operating hours. kWh counters, power
ups, etc.
ID-00 Operating hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned off.
ID-01 Running Hours
Range:
Function:
0 h
*
[0 - 2147483647
h]
View how many hours the motor has
run. Reset the counter in
ID-07 Reset
Running Hours Counter
. The value is
saved when the frequency converter is
turned off.
ID-02 kWh Counter
Range:
Function:
0 kWh
*
[0 - 2147483647
kWh]
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in
ID-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647] View the number of times the frequency
converter has been powered up.
ID-04 Over Temp's
Range:
Function:
0
*
[0 - 65535] View the number of frequency converter
temperature faults which have occurred.
ID-05 Over Volt's
Range:
Function:
0
*
[0 - 65535] View the number of frequency converter
overvoltages which have occurred.
ID-06 Reset kWh Counter
Option:
Function:
[0]
*
Do not reset
Nno reset of the kWh counter is desired.
[1]
Reset counter Press [OK] to reset the kWh counter to zero
(see
Parameter Descriptions
AF-650 GP Programming Guide
108
DET-618C
3