After selecting “OK” the network “GE” should show up under Networks and by selecting the Network, the main configuration page will be shown.
In this menu the following settings have to be made:
Menu
Menu point
Setting
Model Family
Model Family
NOE 0100, NOE 110
Model Utilities
IO Scanning
YES
Global Data
NO
Address Server
NO
IP address configuration
Configured/From a server
Configured
IP address
192.168.001.020
Subnetwork mask
255.255.255.0
Gateway address
0.0.0.0
Ethernet Configuration
Ethernet Configuration
Ethernet II
In the IP Configuration tab, the “Configured” bottom has to be selected, and the IP address and Subnetwork mask has to be filed out. In this example the address
192.168.1.20 is used as the address for the master.
The step assigns the protocol to the scanner,
which is done by selecting the scanner and selecting the “Function” menu and enables the Ethernet by selecting “ETH
TCP IP” This brings up the Net Link menu, where “GE” has to be selected. At this time the “GE” Protocol is assign to the Scanner and the last step is to configure the
scanner to read and write holding registers of the AF-650 GP.
Modbus TCP
18