![GE AF-600 FP Series User Manual Download Page 57](http://html1.mh-extra.com/html/ge/af-600-fp-series/af-600-fp-series_user-manual_3929023057.webp)
57
Table C
6KFP*L Series Non-Bypass Configuration -
Electrical Channel
HP Ratings
Estimated Watt Loss (Watts) at
208V
460V
575V
2
71
68
71
3
101
86
86
5
79
86
91
7.5
111
93
93
10
130
107
93
15
147
130
107
20
172
139
130
25
147
139
101
30
201
142
140
40
380
208
187
50
380
248
198
60
443
248
193
75
-
299
257
100
-
369
373
125
-
369
368
150
-
4014
3902
200
-
4644
4430
250
-
5372
5332
300
-
6369
6247
350
-
7182
7141
400
-
-
7682
450
-
9623
8106
500
-
9701
9140
550
-
10997
-
600
-
11601
10852
650
-
-
10852