102
Advent Commercial Fire System
Contact ID Codes and Event Types
Use Table B.8 for determining event types and CID codes.
Note
Items in grey are not supported.
Table B.8 Contact ID Codes
Description
S
p
e
c
ific
Ty
p
e
Cont
act I
D
Co
de
A
s
soc
iate
d
Zo
ne T
y
pe
Alarms
(General Types 1–Alarm, 2–Alarm Cancel, 3–Alarm Restoral)
Note
All alarm cancels are reported as CID code 406
*Advent has a defined level that reports “silent burglary” (CID
146). This will be used in place of the defined event code at the
appropriate level.
Unspecified
0
140
Fire
1
110
26, 90
Fire Panic
2
115
60(B), 62,
Touchpad
Panics
Police
3
130
8, 9, 30*, 60(A),
61*, 64*, 75-79*
Police Panic
4
120
0, 1,
Touchpad Panics
Medical
5
100
4-7,
Touchpad Panics
Medical Panic
6
101
54-57,
Touchpad Panics
Auxiliary
7
140
Auxiliary Panic
8
100
4-7,
Touchpad Panics
Tamper
9
144
63*, 65*, 66*, 85,
Any Zone
No Activity
10
102
Suspicion
11
122
2, 3, 58, 73, 74
Buddy
12
140
Low Temperature Limit
13
159
High Temperature Limit
14
158
Keystroke Violation
15
145
Duress
16
121
Exit Fault
17
374
Explosive Gas
18
151
34, 67
Carbon Monoxide
19
162
68
Environmental
20
150
29
Latchkey
21
642
Equipment Tamper
22
137
Holdup
23
122
2, 3, 58, 73, 74
Sprinkler
24
113
82
Heat
25
114
81
Siren Tamper
26
137
Smoke
27
111
80
Repeater
28
144
63*, 65*, 66*, 85,
Any Zone
Fire Pump Activated
29
110
26, 90
Fire Pump Failure
30
140
Fire Gate Valve
31
140
Low CO2 Pressure
32
140
Low Liquid Pressure
33
140
Low Liquid Level
34
140
Entry Exit Intrusion (Police)
35
134
10-12*
Perimeter Intrusion (Police)
37
131
13*
Interior Intrusion (Police)
38
132
14-20*
Fire Trouble
(General Types 4–Zone Trouble Fire, 5–Zone Trouble Restoral
Fire)
Unspecified
0
373
Hardwire Trouble
1
373
Ground Fault
2
310
Device Trouble
3
373
RF Supervisory
4
381
RF Low Battery
5
384
Tamper
6
383
Suspected Sensor Failure
7
373
Partial Obscurity
8
386
RF Jam
9
373
Zone AC Failure
10
373
Zone Low Battery
11
373
NAC Trouble
12
373
Analog Zone Trouble
13
373
Fire Supervisory Trouble
14
200
96
Pump Failure
15
206
91
Gate Valve Closed
16
203
92
CO2 Pressure
17
202
93
Liquid Pressure
18
201
94
Liquid Level
19
204
95
Non-Fire Trouble
(General Types 6–Zone Trouble Non Fire, 7–Zone Trouble
Restoral Non Fire)
Unspecified
0
380
Hardwire Trouble
1
380
Ground Fault
2
310
Device Trouble
3
380
RF Supervisory
4
381
RF Low Battery
5
384
Table B.8 Contact ID Codes (Continued)
Description
S
p
e
c
ific
Ty
p
e
Cont
a
c
t I
D
Co
de
A
s
soc
iate
d
Zo
ne T
y
pe
Summary of Contents for Advent
Page 56: ...54 Advent Commercial Fire System ...
Page 88: ...86 Advent Commercial Fire System ...
Page 110: ...108 Advent Commercial Fire System ...