SCA2000BCC - GE Profile Performance

Advantium

Oven 

Hood Exhaust Duct

Outside ventilation requires a HOOD EXHAUST DUCT. Read the following
carefully.

EXHAUST CONNECTION:

The hood exhaust has been designed to mate with a standard 3-1/4” x 10” 
rectangular duct.

If a round duct is required, a rectangular-to-round transition adaptor must be
used. Do not use less than a 6” diameter duct.

REAR EXHAUST:

If a rear or horizontal exhaust is to be used, care should be taken to align
exhaust with the space between studs, or wall should be prepared at the
time it is constructed by leaving enough space between the wall studs to
accommodate exhaust.

Duct

Equivalent

A.

Rectangular-To-Round

5 Ft.

Transition Adaptor

B.

Wall Cap

40 Ft.

C.

90° Elbow

10 Ft.

D.

45° Elbow

5 Ft.

E.

90° Elbow

25 Ft.

F.

45° Elbow

5 Ft.

G.

Roof Cap

24 Ft.

Grille

Filter Kit Accessory

Filter Kit
JX81A–Recirculating
Charcoal Filter Kit
To be used when 
the Advantium oven 
cannot be vented 
to the outside.

MAXIMUM DUCT LENGTH:

For satisfactory air movement, the total duct length of 3-1/4” x 10” rectangular or
6” diameter round duct should not exceed 140 equivalent feet.

ELBOWS, TRANSITIONS, WALL AND ROOF CAPS

, etc., present additional 

resistance to airflow and are equivalent to a section of straight duct which is
longer than their actual physical size. When calculating the total duct length, add
the equivalent length of all transitions and adaptors plus the length of all straight
duct sections. The chart below shows the approximate feet of equivalent length of
some typical ducts.