Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown here.
LP Vapor (Propane)
10 kW
8 kW
Full Load
Cu Ft/Hr
65.6
56.4
Gal/Hr (liquid)
1.82
1.57
BTU/Hr
164000
141000
1/2 Load
Cu Ft/Hr
42.8
37.6
Gal/Hr (liquid)
1.18
1.04
BTU/Hr
107000
94000
Exercise
Cu Ft/Hr
23.6
20
Gal/Hr (liquid)
0.65
0.55
BTU/Hr
59000
50000
10 kW
8 kW
Full Load
Cu Ft/ Hr
169
121
BTU / Hr
169000
121000
1/2 Load
Cu Ft/ Hr
111
94
BTU / Hr
111000
94000
Exercise
Cu Ft/ Hr
60
53
BTU / Hr
60000
53000
Recommended Energy
Content of Fuel:
Natural Gas
Propane
(LP Vapor)
Heating Value:
BTU per gallon liquid
(gross*)
BTU per Cubic feet
(vapor)
N/A
1,000
91,547
2,500
Natural Gas
Summary of Contents for 40374
Page 10: ...N o t f o r R e p r o d u c t i o n 10 Intentionally Left Blank...
Page 40: ...N o t f o r R e p r o d u c t i o n 40 NOTES...
Page 41: ...N o t f o r R e p r o d u c t i o n 41 Schematic Diagram 10kW Schematic Wiring Diagrams...
Page 42: ...N o t f o r R e p r o d u c t i o n 42 Wiring Diagram 10 kW J12 J19...
Page 43: ...N o t f o r R e p r o d u c t i o n 43 Schematic Diagram 8kW...
Page 54: ...N o t f o r R e p r o d u c t i o n 10 Se dej intencionalmente en blanco...
Page 84: ...N o t f o r R e p r o d u c t i o n 40 Se dej intencionalmente en blanco...
Page 94: ...N o t f o r R e p r o d u c t i o n 10 Laiss en blanc intentionnellement...
Page 124: ...N o t f o r R e p r o d u c t i o n 40 Laiss en blanc intentionnellement...