6–10
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S1 RELAY SETUP
CHAPTER 6: SETPOINTS
passwords (USB port and keypad), or remotely using the Remote passwords (RS485 and
Ethernet ports). The user can have either Setpoint or Control Level access active, but not
both simultaneously from the same interface. Setpoint and Control passwords must be 3
to 10 alphanumeric characters in length. The Master Level is used for setting and resetting
of passwords, and includes all Setpoint and Control Level access rights. The Master
Password must be 8 to 10 characters in length, containing at least 2 letters and 2 numbers.
The Master Level can define whether the local user is permitted to change Local
Passwords without having to enter the Master Level. The Master Password is encrypted,
and is not viewable from the keypad. If the Master Password is lost, the user should
contact the factory.
After password entry, the access level is maintained until a period of 5 minutes of inactivity
has elapsed, after which the password must be re-entered. A power loss or entering in the
wrong password logs the user out.
Further definition of the access levels is described as follows:
SETPOINT LEVEL
•
Changing settings under QUICK SETUP menu
•
Changing settings under the SETPOINTS menu except the features requiring control
access listed below
•
Changing any setting under MAINTENANCE such as trip and close coil monitoring and
breaker maintenance settings, except the features requiring control access listed
below
•
Changing the Local or Remote Setpoint Password, depending on the interface being
accessed
CONTROL LEVEL
•
Open and Close Breaker commands
•
Virtual Input commands
•
Clearing of event records, transient records, and other data
•
Changing the Local or Remote Control Password, depending on the interface being
accessed
MASTER LEVEL
•
Setting and changing of all passwords including the Master Password
•
Disabling password security
•
All Setpoint and Control Level access rights
•
Enabling the Password for Reset Key feature (when enabled, Trip and Alarm resets
require a password)
For details on Password Security setup and handling using the EnerVista Setup software,
refer to Chapter 3.
Access passwords
This section allows the user to change the Local Setpoint and Local Control Passwords, and
to enable the Password for Reset Key feature (requires the Master Password).
The local user may change a local password from the keypad if all of the following are true:
•
Security is enabled
•
A valid local setpoint (or local control) password has initially been set
•
The remote user has the Overwrite Local Passwords setpoint set to
NO
•
The local user knows the current local password.
For more details on the Password Security feature, refer to Chapter 3.