background image

TIMERN

CN O

COM NC2 NO2 COM2

LOAD

L1

L2

TIMERN

CN O

COM

TO 200/240/277V LINE

TO 120V LINE

NC2 NO2 COM2

H

N

LOAD

TIMERN

CN O

COM

TO 24V LINE

NC2 NO2 COM2

H

N

LOAD

N
H

TO 120V LINE

TO LOAD

T

T

T

120V Timer, 120V Load and 24V Load

Wired as Single Throw

200/240/277V Timer, 200/240/277V Load, Double Break

Wired as Single Throw

120V Timer, 200/240/277V Load Double Break

Wired as Single Throw

Typical Wiring Diagrams—DPDT

TO POWER SUPPLY

TO POWER SUPPLY 1

TO POWER SUPPLY 2

Timer and Load, Same Voltage

Wired as Single Throw

TO LOAD

TO 120V LINE

H

N

HIGH

LOW

COM

T

LOAD

T

NC

TIMERN

OC OM

TIMERN

CN OC OM

T

TIMERN

CN OC OM

120V Two Speed Fan

Wired as Double Throw

Timer and Load, Different Voltage

Wired as Single Throw

Typical Wiring Diagrams—SPDT

Field Wiring

Timer Internab Wiring

PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE

INSULATION CLEARS

PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14

12

10

8

15

20

30

40

60

60

60

105

1/2

1

2

-

2

2 1/2

3

5

N/A

N/A

Figure 1

Override 

(Manual ON/OFF Switched)

Timer 

(9 Programs Setting)

Clock 

(Current Time Setting)

LCD 

(Function Figures)

 

(Reset)

H- 

(Hours Setting)

M- 

(Minutes Setting)

Day 

(Days Setting)

Operating Instructions

Basic Settings

Initial Setup:

1.  Push the Reset button 

“R” before programming to clear out any settings. 

Once the 

“Reset” button is pressed the screen will begin to flash. A 

paperclip may be needed for this step.
(If the “Reset” button is shown down, use a paper clip to maneuver it until it 
pops back up. The screen will flash if the button is in its proper position
)

2.  Press the 

“Clock” button and the screen will stop flashing and be ready for 

programming.

Setting the Current Time:

1.  Press and Hold the 

“Clock” button during the entire setting.

2.  Press the 

“H+” button to set the hours.

3.  Press the 

“M+” button to set the minutes.

4.  Press the 

“Day” button to set the day of the week.

5.  Release the 

“Clock” button. 

Programming ON/OFF Settings:

1.  Press the 

“Timer” button once and the TIMER 1 ON - - : - - appears.

2.  Press the 

“H+” and “M+” button to set the hours and minutes to the 

desired time.

3.  Press the 

“Day” button to select the day(s) the setting will be active. Refer 

to the Multiple Weekday Group below to see the available settings.

4.  Press the 

“Timer” button to store the setting and proceed to the next 

setting 

TIMER 1 OFF - - : - -.

5.  Repeat steps 1-4 to program the remaining ON/OFF times setting options 

(9 Total ON/OFF settings). Once completed press the 

“Clock” button to 

return to the main display.

Multiple Weekday Groups:

Apart from individual week days, pressing the “Day” button also selects 
multiple day combinations such as:
‧ Monday  thru  Friday                            

‧ Tuesday & Thursday & Saturday

‧ Saturday &  Sunday                              

‧ Monday thru  Wednesday

‧ Monday  thru  Saturday                      

‧ Thursday thru  Saturday

‧ Monday & Wednesday & Friday            

‧ Monday  thru  Sunday

After setting a single day or a multi-day-combination the programmed timer 
settings will be carried out on each of the week-days at the same time.

15136