ESL 1500 Series Fire Alarm Control Panel

Specifications

General

Operating temperature........................ 0° to 49°C (32° to 120°F)

Housing

Type............................Steel with hinged/removable, locking door

Size..........14.0 in. x 14.0 in. x 4.5 in.(35.6cm x 35.6cm x 11.4cm)

Finish..................................................Red, sand textured, enamel

Weight.................................................... 15 lbs. max. w/o battery

1500-BMB- Basic Master Board

Power

Input power............................................120 VAC, 60Hz, 56 V A

Standby power................................................................ 24 VDC

Auxiliary power output...................... 24 VDC FWR, 1.0 A max.

............................................................(32.1 VDC max. - no load)

Note: 

Auxiliary power output supply is shared with power

for indicating circuit. Consider total requirements.

(I

 

aux

 + I 

IND

#1 + I 

IND

#2 = 1.5 A)

Optional standby battery.................................................. 24 Volt

Battery charger rate.................................................. 700 mA max.

Battery charge voltage................................................... 29 V max.

Alarm initiating circuits

Number of circuits............................................ One - model 1501

                                                                        Three - model 1503

                                                                          Five - model 1505

Type................................... Class A or B, Latched (Style B or D)

End-of-line................................................. 2.7 K Ohms, 1/2 Watt

Loop powered device current........................................... 2.0 mA

Alarm current..................................................................... 15 mA

Maximum current............................................................... 60 mA

Maximum voltage............................................................. 17 Volts

Normal circuit voltage................................................... 14.7 Volts

Minimum voltage.......................................................... 13.5 Volts

Maximum ripple voltage................................. 500 Millivolts AC

Maximum line resistance.....100 Ohms(Compatibility Ident.C01)

                                                Ohms(Compatibility, Ident.C01A)

Alarm indicating circuits

Number of circuits ................... Two Class A or B (Style Y or Z)

Maximum current per circuit......................................... 1.0 Amps

Maximum total current ................................................. 1.5 Amps

Output voltage ..................................................... 24 VDC, FWR

End-of-line ................................................ 2.7 K Ohms, 1/2 Watt

Supplementary alarm/trouble contacts

System trouble ................................... 2.0 A @ 30 VDC resistive

System alarm ...................................... 2.0 A @ 30 VDC resistive

Sounder output

Alarm...................................................................Constant output

Fault ..................................................... -0.25 sec. on; 2.5 sec. off

Supervisory ....................................... -0.25 sec. on; 0.25 sec. off

Remote indicator

Voltage ........................................................................ 12 VDC

Current ................................................................. 15 mA max.

1500-ZEM -  Zone Expander Module

Initiating circuits

Number of circuits ........................................................... Two

Type .............................. Class A or B, latched (Style B or D)

End-of-line............................................ 2.7 K Ohms, 1/2 Watt

Loop powered device current...................................... 2.0 mA

Alarm current ............................................................... 15 mA

Maximum current ......................................................... 60 mA

Maximum voltage ....................................................... 17 Volts

Normal circuit voltage ............................................. 14.7 Volts

Minimum voltage .................................................... 13.5 Volts

Maximum ripple voltage ............................ 500 Millivolts AC

Maximum line resistance

                                      100 Ohms(Compatibility Ident. C01)

                                    50 Ohms (Compatibility Ident. C01A)

Remote Indicator

Voltage ........................................................................ 12 VDC

Current ................................................................. 15 mA max.

1500-LEM - Local Energy Module

Output characteristics

Standby ........................................................ 2 VDC (no load)

Alarm ............................................................... 24 VDC FWR

Trouble ........................................................................ 0 VDC

Alarm current ..................................................... 320 mA max.

Standby current .............................................................. 1 mA

1500-ZRM-5  - Zone Relay Module

Output characteristics

Voltage ........................................................................ 12 VDC

Standby current ............................................. 0 mA per circuit

Alarm current .............................................. 15 mA per circuit

Contact ratings .......................................... 3 A @ 30 VAC/DC

1500-RA-5A - Remote Annunciator

Output Characteristics

Number of zones ......................................... 5 alarm, 1 trouble

Voltage ........................................................................ 12 VDC

Standby current ............................................. 0 mA per circuit

Trouble current ............................................................ 50 mA

Alarm current .............................................. 15 mA per circuit

Summary of Contents for 1501

Page 1: ...ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual GE Security g...

Page 2: ......

Page 3: ...n 6 Supervisory Functions 6 Remote Test Drill 6 Field Wiring 7 Installation Recommendations Precautions 9 Field Wiring Checkout Procedures 10 Alarm Initiating Devices 10 Alarm Indicating Devices 11 Co...

Page 4: ......

Page 5: ...re 10 Terminal Connections 12 Figure 11 Local Energy Module LEM Wiring Diagram 13 Figure 12 BMB Default Settings 13 Figure 13 ZEM Default Settings 14 Figure 14 ZEM Programming Switches Location 14 Tab...

Page 6: ...good mechanical and working order If any application or installation information is not understood or is not covered in this manual please contact Technical Support 800 648 7424 Sales 800 547 2556 Sy...

Page 7: ...e panel 5 initiating circuits 2 indicating circuits 1500 BMB Basic Master Board 1 initiating circuit 2 indicating circuits 1500 ZEM Zone Expansion Module 2 initiating circuits Class A or B 1500 LEM Lo...

Page 8: ...ies Determine the total system power requirements by using the Standby Battery Power Worksheet in Appendix B 9 System Check Make certain the 1500 panel is operating properly before connecting field wi...

Page 9: ...at has not been disabled will activate the indicating devices as normal The zone disconnect switch is defeated when a zone has been programmed for waterflow service See BMB Programming Walktest makes...

Page 10: ...en using alarm verification total alarm delay alarm verification smoke detector power up time cannot exceed 60 seconds according to the National Fire Alarm Code NFPA 72 or 30 seconds for installations...

Page 11: ...red local alarm LED lights In addition the supervisory LED on the BMB will activate During supervisory trouble the integral sounder activates a rapidly pulsing tone zone 2 yellow local trouble LED lig...

Page 12: ...1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 429C 2 7K EOL Resistor 1 2W Pull station Heat sensor 2 7K EOL Resistor 1 2W 449C 449C Z...

Page 13: ...ktest 2 Zone 1 waterflow 1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 521B 429C 521B 2 7K EOL Resistor 1 2W Pull station Heat sensor...

Page 14: ...em to a conduit or green wire circuit that also is used to power resistance heating motors fans air conditioning equipment or florescent lighting circuits since leakage currents into the ground return...

Page 15: ...capable of protecting equipment from damage caused by direct hit strikes of lightning due to the extremely high energy released 10 million to 100 million volts 10 000 to 30 000 amps However line surge...

Page 16: ...15 or 3 16 diameter drill and deburr 4 Install the supplied push rivets from the outside of the cabinet through both the cabinet side wall and the snap track driving the push pins flush with the rivet...

Page 17: ...1 trouble Supervisory Low no AC Low no battery Ground fault Indicating 1 trouble Indicating 2 trouble 1 2 3 4 5 6 7 8 9 10 1 Mounting hole 2 Basic Master Board BMB 3 Housing backbox 4 Programming swi...

Page 18: ...le LEM trip circuit is designed to interface to a Listed Master Box with a local energy trip mechanism This optional module provides a supervised trip circuit from the 1500 system that activates the M...

Page 19: ...1500 BMB is disabled See Supervisory Functions 2 on zone 3 5 Remote Connection to remote indicator not supervised Annunciator 1 on zone 2 4 Remote Connection to remote indicator not supervised Annunci...

Page 20: ...the batteries Maintenance Batteries The 1500 Series control unit uses two sealed lead acid batteries as the secondary power source The batteries must be replaced if the Low Battery LED remains on for...

Page 21: ...o low upgrade or move to new circuit Low No AC power LowAC power If secondary shows less than 22 VAC replace transformer System trouble LED Less than 94 VAC at transformer primary no load Trouble soun...

Page 22: ...e Y or Z Maximum current per circuit 1 0 Amps Maximum total current 1 5 Amps Output voltage 24 VDC FWR End of line 2 7 K Ohms 1 2 Watt Supplementary alarm trouble contacts System trouble 2 0 A 30 VDC...

Page 23: ...tectors shown in Table 10 Table 8 Compatible Indicating Devices Manufacturer Part Number Amseco SLB24 75C Amseco SLB24G 75C Amseco SMS1 3A EST G1 R HOV110 EST G1 R HOV15 EST G1 R HOV75 EST G1 R V15 ES...

Page 24: ...lity Identifier per Circuit Ohms Identifier ESL 400 Series 429C 429CT 100 C01 S10A 20 Self Diagnostic 429CRT 429CST 100 C01 S11A 20 ESL 500 Series 521B 521NB 100 C01 DIP SW 1 ON S09A 20 and ESL 500N S...

Page 25: ...1000 mA mA Auxiliary System Power mA 1 Amp 1000 mA mA 1500 ZEM Zone 2 8 mA mA 70 mA mA 1500 ZEM Zone 3 8 mA mA 70 mA mA 1500 ZEM Zone 4 8 mA mA 70 mA mA 1500 ZEM Zone 5 8 mA mA 70 mA mA 1500 LEM 1 mA...

Page 26: ...from any other zone is not affected Alarm Disconnect Switch Operated After Alarm Condition For Maintenance Use Only Auxiliary alarm relay contacts remain latched Alarm indicating circuits are turned O...

Page 27: ......

Page 28: ...2603 Rev J 04 04 64812687 Rev J Tech Support 800 648 7424 FaxBack 800 483 2495 www GESecurity com GE Security 12345 SW Leveton Drive Tualatin OR 97062 503 692 4052 USA Canada 800 547 2556 GE Security...

Reviews: