ESL 1500 Series Fire Alarm Control Panel
Connecting Optional Remote Notification Devices
1500-RA-5A
Note:
When using remote annunciators other than the ESL 1500-RA-5A, be sure all circuits have a series resistance of at
least 1K ohm. Maximum current should be 15mA per zone.
The control unit can properly power one remote annunciator. When a remote annunciator is used, both the BMB and ZEM
must be programmed to provide supervision. See Programming. The remote annunciator circuit is supervised as long as no other
devices are connected to the same terminals; otherwise, the devices will not be supervised. See Figure 10 for the wiring diagram.
1500-LEM
The Local Energy Module (LEM) trip circuit is designed to interface to a Listed Master Box with a local energy trip mechanism.
This optional module provides a supervised trip circuit from the 1500 system that activates the Master Box upon a system
alarm. Make connections as detailed in Figure 11.
For systems which include remote annunciation 1500-RA-5A, use Figure 10. Remove all power from the system before
beginning procedure.
Figure 12. BMB Default Settings
1
2
K2
I
R9
+
Figure 11. Local Energy Module (LEM) Wiring Diagram
TB1 (opposite side)
Local Energy Master box trip
module (LEM)
Master box trip coil 14.6
Ohms, 24 VDC 0.26A
min. 0.35A max.
City fire alarm ckt.
Max. line resistance 10 Ohms
- 24 V alarm output
P5
DS1 (trouble)
Normal
Disconnect
ON
1
2
3
4
5
6
7
8
8-Not used
7-Not used
6-Not used
5-Zone 2 Supervisory
4-Zone 1 Remote Annunciator
3-Silent Walktest
2-Zone 1 Waterflow
1-Alarm Verification