3.2 ELECTRICAL
The sensors are connected to the turbine junction box with connector cable RS-E2-0285 or equivalent. The
RS-E2-0285 consists of black, white and green wires twisted and shielded. All wiring must be in grounded
conduit. The green wire must be connected to earth ground at the junction box. Do not connect the shields to
each other or to earth ground at any location. The shields should be individually jumped through all junction
boxes and connected to the proper ground terminal at the Controller. The polarity of the cable is as follows;
white is positive and black is negative/signal return. Reverse polarity will not damage the sensor. Signal cable
from the junction box to the Controller should be 18 gauge (1.02 mm) twisted shielded pair. The extension
cable from the junction box to the Controller is the customer’s responsibility.