B-46
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7FA2
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7FA3
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7FA4
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7FA5
Auxiliary Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7FA7
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7FA8
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7FA9
Reserved (8 items)
0 to 65535
---
1
F001
0
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
2 to 90
Hz
---
F001
0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
-55 to 125
C
1
F002
-55
81C1
Reserved Register T2
-55 to 125
C
1
F002
125
81C2
Reserved Register T3
-2147483647 to
2147483647
---
1
F004
0
81C4
Reserved Register T4
0 to 4294967295
---
1
F003
0
81C6
Reserved Register T5
0 to 4294967295
---
1
F003
0
81C8
Reserved Register T6
0 to 4294967295
---
1
F003
0
81CA
Reserved Register T7
0 to 4294967295
---
1
F003
0
81CC
Reserved Register T8
0 to 4294967295
---
1
F003
0
Breaker Failure (Read/Write Grouped Setting) (6 Modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 4294967295
---
1
F300
0
8607
Breaker Failure 1 Block
0 to 4294967295
---
1
F300
0
8609
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860A
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860B
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
8610
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 4294967295
---
1
F300
0
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 4294967295
---
1
F300
0
8615
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
8617
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8619
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861A
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861B
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
861C
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
861D
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
861E
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861F
Breaker Failure 1 Phase A Initiate
0 to 4294967295
---
1
F300
0
8621
Breaker Failure 1 Phase B Initiate
0 to 4294967295
---
1
F300
0
8623
Breaker Failure 1 Phase C Initiate
0 to 4294967295
---
1
F300
0
8625
Breaker Failure 1 Breaker Status 1 Phase B
0 to 4294967295
---
1
F300
0
8627
Breaker Failure 1 Breaker Status 1 Phase C
0 to 4294967295
---
1
F300
0
8629
Breaker Failure 1 Breaker Status 2 Phase B
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...