B-14
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
07EC
...Repeated for IEC103 Command 28
07F0
...Repeated for IEC103 Command 29
07F4
...Repeated for IEC103 Command 30
07F8
...Repeated for IEC103 Command 31
07FC
...Repeated for IEC103 Command 32
Digital Counter States (Read Only Non-Volatile) (8 Modules)
0800
Digital Counter 1 Value
-2147483647 to
2147483647
---
1
F004
0
0802
Digital Counter 1 Frozen
-2147483647 to
2147483647
---
1
F004
0
0804
Digital Counter 1 Frozen Time Stamp
0 to 4294967295
---
1
F050
0
0806
Digital Counter 1 Frozen Time Stamp us
0 to 4294967295
---
1
F003
0
0808
...Repeated for Digital Counter 2
0810
...Repeated for Digital Counter 3
0818
...Repeated for Digital Counter 4
0820
...Repeated for Digital Counter 5
0828
...Repeated for Digital Counter 6
0830
...Repeated for Digital Counter 7
0838
...Repeated for Digital Counter 8
FlexStates (Read Only)
0900
FlexState Bits (16 items)
0 to 65535
---
1
F001
0
Element States (Read Only)
1000
Element Operate States (64 items)
0 to 65535
---
1
F502
0
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
---
---
---
F200
(none)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14E0
Target Sequence
0 to 65535
---
1
F001
0
14E1
Number of Targets
0 to 65535
---
1
F001
0
Element Targets (Read/Write)
14E2
Target to Read
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14E3
Target Message
---
---
---
F200
“.”
Contact Input/Output States (Read Only)
1500
Contact Input States (6 items)
0 to 65535
---
1
F500
0
1508
Virtual Input States (8 items)
0 to 65535
---
1
F500
0
1510
Contact Output States (4 items)
0 to 65535
---
1
F500
0
1518
Contact Output Current States (4 items)
0 to 65535
---
1
F500
0
1520
Contact Output Voltage States (4 items)
0 to 65535
---
1
F500
0
1528
Virtual Output States (6 items)
0 to 65535
---
1
F500
0
1530
Contact Output Detectors (4 items)
0 to 65535
---
1
F500
0
Input/Output States (Read Only)
1540
Remote Device States (2 items)
0 to 65535
---
1
F500
0
1542
Remote Input States (4 items)
0 to 65535
---
1
F500
0
1550
Remote Devices Online
0 to 1
---
1
F126
0 (No)
1551
Remote Double-Point Status Input 1 State
0 to 3
---
1
F605
3 (Bad)
1552
Remote Double-Point Status Input 2 State
0 to 3
---
1
F605
3 (Bad)
1553
Remote Double-Point Status Input 3 State
0 to 3
---
1
F605
3 (Bad)
1554
Remote Double-Point Status Input 4 State
0 to 3
---
1
F605
3 (Bad)
1555
Remote Double-Point Status Input 5 State
0 to 3
---
1
F605
3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0
Direct Input States (6 items)
0 to 65535
---
1
F500
0
15C8
Direct Outputs Average Message Return Time 1
0 to 65535
ms
1
F001
0
15C9
Direct Outputs Average Message Return Time 2
0 to 65535
ms
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 6 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...