5–6
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.1.2
Trips, Alarms, and Blocks
The 469 has three basic categories of protection elements. They are
trips
,
alarms
, and
blocks
.
•
TRIPS:
A 469 trip feature may be assigned to any combination of the two Auxiliary
relays, 2 AUXILIARY and 3 AUXILIARY, in addition to the 1 TRIP Relay. If a Trip becomes
active, the appropriate LED (indicator) on the 469 faceplate will illuminate to show
which of the output relays has operated. In addition to the Trip relay(s), a trip will
always operate the Block Start relay. Trip features are may be programmed as latched
or unlatched. Once a relay has been operated by a latched trip, a reset must be
performed to clear the trip when the condition is no longer present. If there is a lockout
time, the Block Start relay will not reset until the lockout time has expired. If an
unlatched trip feature becomes active, that trip will reset itself (and associated output
relays) as soon as the condition that caused the trip ceases. Immediately prior to
issuing a trip, the 469 takes a snapshot of motor parameters and stores them as pre-
trip values which will allow for troubleshooting after the trip occurs. The cause of last
trip message is updated with the current trip and the 469 display defaults to that
message. All trip features are automatically logged and date and time stamped as
they occur. In addition, all trips are counted and logged as statistics such that any long
term trends may be identified.
•
ALARMS:
A 469 alarm feature may be assigned to operate any combination of three
output relays, 4 ALARM, 3 AUXILIARY, and 2 AUXILIARY. When an Alarm becomes
active, the appropriate LED (indicator) on the 469 faceplate will illuminate when an
output relay(s) has operated. Each alarm feature may be programmed as latched or
unlatched. Once a latched alarm feature becomes active, the reset key must be
pressed to reset that alarm. If the condition that has caused the alarm is still present
(e.g. hot RTD) the Alarm relay(s) will not reset until the condition is no longer present. If
MESSAGE
TEST
[
MESSAGE
COMMUNICATION
[
MESSAGE
GE
MULTILIN
[
Z
]
MESSAGE
END OF PAGE
SETTINGS
[
SPEED2
[
MESSAGE
SPEED2
[
MESSAGE
SPEED2
[
MESSAGE
END OF PAGE
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...