Critical Power
Modifications reserved
Page 49/60
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Installation Guide
TLE Series 160 - 500 UL S2B
Fig. 4.9.2-2 Bus connection on first and last units
Final units, first and last, of a RPA Parallel System
On the two boards
P13/P14 – IM0022 – Bus Interface Board
, of the first and last units of a
Parallel
System
, the switches
SW1-1/2/3/4/5/6
MUST BE IN POSITION ON
(see
Fig. 4.9.2-2
).
Fig. 4.9.2-3 Bus connection on intermediate units
Intermediate units of a RPA Parallel System
On the two boards
P13/P14 – IM0022 – Bus Interface Board
, of the intermediate units of a
Parallel
System
, the switches
SW1-1/2/3/4/5/6
MUST BE IN POSITION OFF
(see
Fig. 4.9.2-3
).