Test operation and after
installation check

Before testing:
1. Do not turn power on until installation is

completely finished.

2. Electric wiring must be connected

correctly and securely.

3. Open all cut-off valves on the connection

pipes.

4. All impurities and debris such as scraps

and filings must be cleared from the unit.

Test operation method:
1. On models other than GE AIR 116, GE

AIR 121, PRO AIR I109 and PRO AIR I112
a. Remove the surface panel of indoor

unit,

b. Use a screw driver to set the switch on

the right of the unit to RUN.

2. Switch power on and press ON/OFF

button on the remote controller.

3. Press MODE button and check the

operating condition of each of the COOL,
HEAT and FAN modes. The HEAT mode is
not available on models GE AIR 326 and
GE AIR 428.

4. If the remote control cannot be used,

employ the following forced operation:

a. For models GE AIR 116, GE AIR 121,

PRO AIR I109 and PRO AIR I112
- With the unit stopped, remove the

surface panel and switch the unit to
AUTO mode by pressing the button
located on the right.

- The unit will automatically run in

the mode selected by the
microcomputer according to the
surrounding temperature.

- With the unit running, press the

button to turn the unit off.

b. For all other models:

- With the unit stopped, remove the

surface panel and set switch on the
right of the unit to AUTO mode.

- The unit will automatically run in

the mode selected by the
microcomputer according to the
surrounding temperature.

- With the unit running, set the

switch to STOP to turn the unit off.

- Once the tests are completed, set

switch to RUN for normal
operations. If the switch is not set
to RUN, the unit will start
automatically every time it is
connected to the power grid or
after a power cut.

AUTO

TEST

R U N

STOP

Air purging and leakage test
For models with multiple indoor units, this
procedure must be executed for each indoor
unit. This procedure requires a manifold
valve and a vacuum pump.

1. Make sure the liquid side valve and gas

side valve are set to the closed position
and check pipes are connected properly.

2. Remove service port nut and connect

manifold valve to the service port of the
3-way valve using a charge hose.

3. Connect manifold valve to the vacuum

pump using another charge hose.

4. Fully open handle Lo on the manifold

valve and run the vacuum pump.

5. Loosen the flare nut of the outdoor unit 

3-way valve and check that air
penetrates. If air does not penetrate,
check charge hose is firmly connected 
to the service port. Tighten the flare nut.

6. Evacuate the circuit for about 15 minutes

with the vacuum pump. Make sure
compound pressure gauge reads minus
760 mm Hg.

7. When evacuation is complete fully close

handle Lo on manifold valve. Then stop
vacuum pump and disconnect it.

8. First open the liquid side valve completely

then 30 seconds after open the gas side
valve fully.

9. Check connections are not leaking using

soapy water or a special leak spray.
Bubbles indicate leak.

Outdoor condensation drainage space 
(not applicable to models GE AIR 326 and 
GE AIR 428)

When the unit is heating or defrosting, the
wastewater formed in the outdoor unit can
be removed through the drain hose. If the
wastewater cannot be drained properly
from the base plate, the defrosting will be
incomplete and the heating capacity of the
unit could be reduced significantly.

Installation: install the outdoor drain elbow
on the Ø 25 millimeter hole on the base
plate as shown in Fig. 4, and join the drain
hose to the elbow, so that the wastewater
formed in the outdoor unit can be drained to
the appropriate place.

Fig. 4

Summary of Contents for GE AIR 107

Page 1: ...Wall Mounted Split Air Conditioner Owner s Manual and Installation Instructions GE Consumer Industrial Appliances GE imagination at work English ...

Page 2: ...How to insert batteries 10 User notices 10 Care and maintenance 11 Troubleshooting 13 Installation instructions 15 Accessories and installation diagram 15 General installation instructions 16 Installing the indoor unit s 18 Installing the outdoor unit 23 Test operation and after installation check 25 Technical specifications 27 Models covered in this document GE GE AIR 107 GE AIR 109 GE AIR 112 GE ...

Page 3: ...alled at least 2 0 m from the ground Extreme temperature differentials can be harmful to health Do not use the air conditioner for drying clothes preserving foods or other functions for which it was not designed Splashing water on the unit may cause an electric shock and malfunction The ground earthing wire must be properly connected Do not connect the earth wire to a gas or water pipe lightning r...

Page 4: ...0 C HEAT mode not available on models GE AIR 326 and GE AIR 428 3 MODE button Select the desired mode of operation by pushing this button The unit can operate on AUTO COOL DRY FAN or HEAT modes Heat mode not available on models GE AIR 326 and GE AIR 428 4 FAN button Press this button to change fan speed There are three speeds to choose from or set the FAN to AUTO to let the unit control the air flo...

Page 5: ...control the speed of the indoor fan according to the target temperature HEAT mode operation not available on models GE AIR 326 and GE AIR 428 The microcomputer automatically controls the rate of heating It adjusts the operation of the unit according to the actual room temperature and the desired temperature If the room temperature is lower than the desired temperature the unit will heat the air of...

Page 6: ...emperature to save energy Keep the room approximately 5 C cooler than the outside temperature when operating in COOL mode Adjust the direction of the airflow appropriately Remember that warm air rises and cool air sinks so adjust the louver downward for heating and upward for cooling to take advantage of natural convection currents User notices CAUTION Always turn power off and remove the power plu...

Page 7: ...enter Please check for the following 1 Is a power connection loose 2 Is the circuit breaker activated 3 Is the voltage higher than 253 volts or lower than 198 volts 4 Is TIMER ON in operation 1 Is the set temperature suitable 2 Is the air inlet or outlet obstructed 3 Are the air filters dirty or clogged 4 Is the indoor fan speed set too low 5 Is there another heat source in the room 1 Is the remote...

Page 8: ... 2 5 4 5 Tapping screw 10 10 20 30 40 Plastic drain hose 1 1 2 3 4 Piping hole sleeve 2 2 4 6 8 Wrapping tape 1 1 2 3 4 Connection piping 1 1 2 3 4 Thermal insulation hose 1 1 2 3 4 Outdoor drain elbow 1 1 2 Outdoor drain stem 2 2 4 Air cleaner 2 2 4 6 8 Square ring 1 2 2 2 Immediately stop all operations disconnect the power and contact your nearest service center in the event any of the followin...

Page 9: ...er before beginning installation to avoid possible malfunctions When picking up and moving the unit be guided by trained and qualified personnel The ground connection of the air conditioner must be made correctly and securely to the recommended earth ground points Contact the service center if you have any question Installation in the following places may cause malfunction Any place where machine o...

Page 10: ...ter 11 Do not install the unit in the immediate vicinity of a laundry bath shower or swimming pool 12 The power plug must be accessible after the appliance is correctly positioned Install the rear panel 1 Always mount the rear panel horizontally 2 Fix the rear panel on the selected location with the screws supplied with the unit 3 Be sure the rear panel is firmly fixed The mounting must be able to w...

Page 11: ...d value to operate the air conditioner safely 7 Wiring work must conform to national standards Model GE AIR 107 GE AIR 109 GE AIR 112 PRO AIR 107 PRO AIR 109 PRO AIR 112 GE AIR 116 GE AIR 121 GE AIR 218 GE AIR 224 PRO AIR 218 GE AIR 326 GE AIR 428 PRO AIR I109 PRO AIR I112 Indoor terminal block N 2 4 5 ground N 2 3 4 5 N 2 3 ground N 1 2 3 ground N 1 2 3 ground Cable wire Blue black violet orange ...

Page 12: ...the connecting cable when fixing it with the wire clamp Make sure the wires are securely connected to the terminal block and the connecting cable is firmly held by the wire clamp Installing the outdoor unit Fig 3 Pipe diameter Torque mm Nm 6 35 15 20 9 52 31 35 12 7 50 55 15 8 60 65 Table 3 Install the piping hole 1 Make the piping hole Ø100 mm for models GE AIR 116 and GE AIR 121 and Ø80 mm for all...

Page 13: ...it is connected to the power grid or after a power cut AUTO TEST R U N STOP Air purging and leakage test For models with multiple indoor units this procedure must be executed for each indoor unit This procedure requires a manifold valve and a vacuum pump 1 Make sure the liquid side valve and gas side valve are set to the closed position and check pipes are connected properly 2 Remove service port ...

Page 14: ...in well Is the voltage in accordance with the rated voltage marked on the nameplate Is the electrical wiring and piping connection installed correctly and securely Has the ground connection been made securely to recommended earth ground points Is the power cord as specified Are the air inlet and outlet blocked Has the length of the connection pipe and the thermal capacity been verified Possible cons...

Page 15: ...770x250x180 770x250x180 770x250x180 907x290x195 907x290x195 770x250x180 770x250x180 770x250x180 770x250x180 Net weight outdoor unit kg 32 32 40 59 59 65 72 71 71 Unit dimensions outdoor unit mm wxhxd 848x540x260 848x540x260 848x540x260 950x700x340 950x840x340 950x700x340 950x840x340 950x840x340 950x840x340 All of the above information may be changed without notice The specifications on the nameplat...

Page 16: ...30 ...

Reviews: