GDS-IR / LPI Infrared Sensor with  

Loop-powered Indicator 

[email protected]

IMPORTANT

 - 

Before installing the GDS-IR / LPI, make sure 

there are no toxic or combustible gases are present. 

 

Factors such as air movement, prevailing winds, convection, gas 

density and emission sources should be taken into account when 

determining sensor location. As with all sensors, the GDS-IR / LPI 

should be protected from falling or directed water, snow, shock, 

vibration and dirt. 
The GDS-IR / LPI sensor may be mounted horizontally or 

vertically (preferred). If horizontal, make sure the GDS-IR is 

protected from dripping water. The Loop Powered Indicator LCD 

can be rotated 90 degrees by opening the display cover, pulling 

firmly on the display electronics, rotating the display and re-

installing (see Fig 2).  
Use conduit and installation practices approved for the 

appropriate area classification. When installed correctly, the GDS-

IR / LPI is suitable for use in areas rated Class 1, Div 1, Groups B, 

C & D.  

Unscrew the cover from the LPI junction box. Firmly grasp the 

display module and pull forward. The display module should 

readily pop free from the mounting posts (see Figure 2).   

NOTE: It is NOT necessary to remove any screws to 

disassemble the Loop Powered Indicator

 

Connect the +DC power wire to TB1-1. Connect the DC power 

common to TB1-2. The allowable DC voltage is +18 to +30 VDC 

(See Figure 3). 
The GDS-IR 4-20mA output signal is available at TB1-5. 

Terminals 3 and 4 should remain shorted on the field wiring side . 

NOTE: 

The GDS-54 Loop Powered Indicator is wired to TB1 via a 

‘plug-in’ two position terminal strip. The terminal strip may contain 

an optional built-in bypass zener diode that allows the display 

module to be removed from the circuit without interrupting the 

primary 4-20mA current loop.  

NOTE: 

The GDS-54 Loop Powered Indicator does 

not 

provide 

calibration capability for the GDS-IR 4-20mA output. If calibration, 

adjustment, alarm relays or MODBUS® serial interface is 

required, see the GDS Corp GASMAX II / GDS-IR gas monitor

.  

Fig 2. Loop Powered Indicator Module 

INSTALLATION 

POWER & 4-20mA WIRING 

GDS-54 “PLUG-IN” 

DISPLAY MODULE 

NEMA 7 ENCLOSURE 

(SIDE VIEW) 

MOUNTING POST  

(4 PLCS) 

TERMINAL 

STRIP TB1 

Auto-Zero 

Magnetic 

Switch 

GDS-IR 

Infrared 

Detector 

Field Wiring Input 

Fig 1. GDS-IR / LPI 

Loop-

Powered 

Indicator 

Calibration Port 

Note: Unit can be configured 

for top conduit entry (shown) or 

side conduit entry (standard). 