GDS GasVac 311 Operating Handbook Download Page 4

4

Installation 

The unit should be mounted in a position which is accessible and in the field of vision. Mains should 
be from a fused supply (2A) and connected to the mains input terminals of the power supply unit.
The vent port should be piped to atmosphere without reduction. This will prevent possible back 
pressure affecting the sensor reading.

A minimum of two intake modules 

should be located within the target area, their position will 

be depedant upon the type of gas to be monitored and its density with respect to air.
Heavy gases (LPG, Propane, Butane, Refrigerant Gases) – locate at 15 to 20 cm from the floor. 
Lighter gases (Methane, Natural Gas, Town Gas) – locate at 5 to 10 cm from the ceiling. 
Carbon Monoxide – locate at 1.5 to 2 metres from floor level.
The control panel should be mounted away from direct heat.

Operation

On power up the green power indicator will flash for 60 seconds indicating that the system is 
stabilising. During this period all alarms are held in the off position.

After the stabilisation period any gas detected by the sensor will be indicated on the display, with 
any alarm level being exceeded resulting in the sounder and appropriate red alarm LED and relay 
activating.

Pressing the reset pad will result in the sounder being silenced. Alarm indicators and relays may 
only be reset when the indicated gas level has reduced to below that of the alarm trip points.

A reduced power mode feature is activated one hour after any operator activity. This state is 
indicated by a screen power reduction of approximately 50%. Pressing any button will return the 
screen to full display.

4-20

OV

Lo

Hi

24V

NO

AL3

NC

NO

C

 

NC

NO

AL2

NC

NO

AL1

NC

W

+

sig

P

-

SENSOR

FAULT

+    -

4-20mA

Output

PC comms via 
hyperterminal

Sensor 

Voltage 

test pins

Zero LED

4mA

J28

20mA

Zero

Gain

J3

J29

J11

J18

J17

J16

J15

J19

J1

TP3

A    B

A
B

A
B

TP11

TP12

TP6

TP7

TP13

TP8 TP9

TP2

TP4

TP1

Contrast

J6

J20

J5

J4

J7

J12

J13

J14

J8

J8

x fault

Inhibit Ov

24v

J1 

CANbus – EOL – see Combi

J4/7  For Semiconductor sensors
J5/11  Sensor (B-catalytic A-4~20mA)
J6/20  Sink/Source 4~20mA output
J8 

Gain – factory set

J9  

Normally fitted 4~20mA out

J12  Bridge fault enable fit for catalytic sensor
J13   See J8
J14  Sensor supply selector

for catalytic sensor

for 4~20mA sensor

J15   Sounder mute
J16   N/E - A1 relay link on
J17    N/E - A2 relay link on
J18   N/E - A3 relay link on
J19   N/E - fault relay link on
J28   Reset processor
J29   Address change enable – see Combi

A
B

4~20mA In

Sensor 
supply 
adjust

4~20mA 

Output

Fig 2

Summary of Contents for GasVac 311

Page 1: ...LTD FUSION POINT ASH LANE GARFORTH LEEDS LS25 2GA UK www gds technologies co uk This document is not contractual and the equipment specification may be modified at any time without prior notice C1732 Manual No 330DIC Issue A v1 GasVac 311 SINGLE LINE NETWORK GAS SAMPLE UNIT OPERATING HANDBOOK ...

Page 2: ...2 Contents System Overview 3 Installation Operation 4 Access to the Menu 5 Technical Specification 6 7 Service Routine Attention 8 ...

Page 3: ...continuously extracted via a unique micropore sample technique having a minimum of two and maximum of 30 intake modules along its sample line network The sampling unit provides a gas level reading with three alarm trip points and a range of signal outputs for annunciator or control functions The system is supplied factory programmed and pre calibrated to enable immediate operation by connection of...

Page 4: ...under and appropriate red alarm LED and relay activating Pressing the reset pad will result in the sounder being silenced Alarm indicators and relays may only be reset when the indicated gas level has reduced to below that of the alarm trip points A reduced power mode feature is activated one hour after any operator activity This state is indicated by a screen power reduction of approximately 50 P...

Page 5: ...entry and exit point of menu 6 L C D Brightness adjustment of display brightness 7 L E D Relay Test turns indicators and relays ON 8 Auto Zero use only when very low alarm levels are required 10 of scale 9 Sensor Address used when connecting to a GDS Combi system A 4 20mA output adjust Tox O2 only Pressing 1 or 3 will allow for output to be adjusted to 4mA and 20mA as measured on test pins 8 9 Cha...

Page 6: ...d unlatched option select before power up see fig 2 Relay flow fail S P C O flow fail alarm board All contacts rated 3A 230v AC All relay contacts used to switch inductive loads relays etc should have suppressors fitted typical device Farnell 772 756 Output 24v DC 100mA Available for auxiliary equipment 4 20mA analogue output CANbus see Combi alarm systems Logging variable time rollover stop Stora...

Page 7: ...m L 32mm D Connections push fit 6mm SAMPLE LINE Material Nylon Stainless Steel Copper Size 6 mm OD 4 mm ID push fit coupling SAMPLE NETWORK LENGTH 100m total SAMPLE VENT PIPE 6 8 mm push fit OPTIONS Catch pot Water auto drain Waterproof over housing IP66 Sample line flame arrestor Snorkel valve water trap Sensor Exhaust Particulate filter Sample in Power board Alarm Monitor PCB 24v DC 24v DC suppl...

Page 8: ... catch pot where fitted for high levels of particulate or water contamination replace filters as necessary Twice yearly maintenance schedule 1 Zero check to sensor 2 Sensor to be gas tested and calibrated 3 Test gas applied to all intake modules 4 Field indicators to be tested 5 Alarm trip points checked and re aligned 6 All faulty parts replaced where required 7 All filter elements checked and re...

Page 9: ... T 44 0 113 286 0166 GDS TECHNOLOGIES LTD FUSION POINT ASH LANE GARFORTH LEEDS LS25 2GA UK www gds technologies co uk This document is not contractual and the equipment specification may be modified at any time without prior notice ...

Reviews: