Note: EOL (4mA End of Line Resistor
A
– 4K7)
CLR (16mA Current Limiting Resistor
B
– 1K5)
Technical Sheet
ref C1694C
+ve In
4
→
16mA
+ve Out
_ve In/Out
Fit EOL Resistor 4K7
W
Y
P
+
Sig
0v
0v
Flt
Fit CLR1K5
Direct sensor
input terminals
Addressable sensor
PCB input terminals
Fit key switch for sensor reset
(see testing the detector)
24v DC
24v DC
(B)
(B)
(C)
N/C
(C)
(A)
S
+
(A)
+ve Out
_ve In/Out
Fit EOL Resistor 4K7
+ve Out
_ve In/Out
Alarm
Contact
N/O
+ve Out
_ve In/Out
+ve Out
_ve In/Out
+ve In
+ve In
+ve In
+ve In
Last sensor
Connecting more than one sensor
Fit CLR1K5
W
Y
P
+
Sig
0v
4-20
Sig
+
24+
SENSOR
SENSOR SPECIFICATION CSD-2
Operating voltage ...................................................................................................................... 24VDC
Average current consumption in quiescent state ...................................................................... < 50μA
Class (for the heat part, in accordance with EN54-5/7) ....................................................... A1/R
Protected area (in accordance with EN54-5/7) ..................................................................... up 120m²
Installation height (in accordance with EN54-5/7) ................................................................ up 16m
Degree of protection ................................................................................................................... IP30
Operational temperature range ................................................................................................ -10 C
+
+60 C
Relative humidity resistance ....................................................................................................... (93 ± 3)% @ 40 C
Dimensions (incl. base) ............................................................................................................... ø102mm, h 48mm
Weight (incl. base)...................................................................................................................... 160g
OPERATION CSD-2 GAS ALARM PANEL SIGNALING
Under normal operating conditions a loop current of approximately 4mA (zero signal) is generated by resistor
(B)
(1K5) and the
EOL resistor
(A)
(4K7) all
(A)
resistors other than for the last device should be removed. When in alarm condition any triggered
device will short circuit the end of line resistor allowing the 1K5 CLR
(B)
resistor to take priority increasing the loop current to
approximately 16mA and signal the alarm panel. A momentary key switch
(C)
is required for device reset.
CONNECTION DETAIL FOR GDS ALARM PANELS (Fig. 6)
For addressable sensors use with one of the following GDS 4~20mA input sensors 171-400 / 168-400 / 170-400