Note:  EOL (4mA End of Line Resistor 

A

 – 4K7)

 

CLR (16mA Current Limiting Resistor 

– 1K5)

Technical Sheet

ref C1694C

+ve In

→ 

16mA

+ve Out

_ve In/Out

Fit EOL Resistor 4K7

W

Y

P

+

Sig

0v

0v
Flt

Fit CLR1K5 

Direct sensor

input terminals

Addressable sensor

PCB input terminals

Fit key switch for sensor reset

(see testing the detector)

24v DC

24v DC

(B)

(B)

(C)

N/C

(C)

(A)

S

+

(A)

+ve Out

_ve In/Out

Fit EOL Resistor 4K7

+ve Out

_ve In/Out

Alarm

Contact

N/O

+ve Out

_ve In/Out

+ve Out

_ve In/Out

+ve In

+ve In

+ve In

+ve In

Last sensor

Connecting more than one sensor

Fit CLR1K5 

W

Y

P

+

Sig

0v

4-20

Sig

+

24+

SENSOR

SENSOR SPECIFICATION CSD-2

Operating voltage ...................................................................................................................... 24VDC
Average current consumption in quiescent state ...................................................................... < 50μA
Class (for the heat part, in accordance with EN54-5/7) ....................................................... A1/R
Protected area (in accordance with EN54-5/7) ..................................................................... up 120m²
Installation height (in accordance with EN54-5/7) ................................................................ up 16m
Degree of protection ................................................................................................................... IP30
Operational temperature range ................................................................................................ -10 C 

+

 +60 C

Relative humidity resistance ....................................................................................................... (93 ± 3)% @ 40 C
Dimensions (incl. base) ............................................................................................................... ø102mm, h 48mm
Weight (incl. base)...................................................................................................................... 160g

OPERATION CSD-2 GAS ALARM PANEL SIGNALING

Under normal operating conditions a loop current of approximately 4mA (zero signal) is generated by resistor

 (B) 

(1K5) and the 

EOL resistor 

(A)

 (4K7) all 

(A)

 resistors other than for the last device should be removed. When in alarm condition any triggered 

device will short circuit the end of line resistor allowing the 1K5 CLR 

(B)

 resistor to take priority increasing the loop current to 

approximately 16mA and signal the alarm panel. A momentary key switch 

(C)

 is required for device reset.

CONNECTION DETAIL FOR GDS ALARM PANELS (Fig. 6)

For addressable sensors use with one of the following GDS 4~20mA input sensors 171-400 / 168-400 / 170-400