background image

22

Fig. 11

XDI–XDIwin – 15/30J

4~20mA INPUT

Set up procedure: 204D2C Issue Tv3

Technical Sheet

 

ref C1180

NEW UNITS ARE SUPPLIED READY TO CONNECT TO A SYSTEM. THE FOLLOWING PROCEDURE MAY NEED TO BE CARRIED OUT 
FOLLOWING CHANGES TO THE SYSTEM:
1.  Insert J8 jumper to receive signal from external 4~20mA source (Fig.3)
2.  Connect external 4~20mA source to the 4~20mA input terminal (J11) on the right hand side of the board.
3.  Connect terminal J10 as shown in Fig.2
4.  Connect DVM (mV range) across TP7 + TP15 to measure current supplied by 4~20mA device (mV = mA)
5.  Ensure that the CAN LED is ON and flashing occasionally.
6.  Connect RS232 pod to connector J3 and to a PC running HyperTerminal at 4800 baud.
7.  The HyperTerminal display shows a continuous data output and allows input from the PC keyboard.

a.  Press C to enter calibration mode 
b.  Press shift $ to initialise the memory if new PCB (defaults to Flam %LEL)
c.  Press G to change gas/signal to the type required for the cell/unit in use. (NOTE: When using a ‘user gas’ press ‘E’ to edit name after 

using ‘G’ to select. Also make sure to select a vacant user gas number, 61–68, as the addressable sensor will overwrite data entered 

at the Combi panel.

d.  The range of the gas/signal selected will have a default setting which can be changed by pressing ‘R’
e.  Press A and enter CAN address of this sensor
f.  Press N to toggle the number of decimal places between 1 and 2 (i.e. dp=1 or dp=2)
g.  Press B to toggle the deadband ON and OFF
h.  Press F to toggle the external fault option ON or OFF (only available when external source has local fault indication)
i.   With input signal reading 4mA press Z to zero the reading.
j.  Press S to span the reading. Apply gas / signal from external source and press H or L to adjust the reading.
k.  Press space to exit the span.
l.  Press X to exit the calibration mode.

8.  Connect to a combi panel and ensure that the sensor reports in correctly. 

Note:

 that if this sensor is at the end of the communication 

wires then it will need terminating by inserting jumper J1(EOL). The continuous data output when connected to HyperTerminal is the same 
format as for the Flammable sensor. The software used is identical.

Fig.1

Fig.2

Fig.3

A

EOL

CAN

4-20

MPU

FAULT

TP1

OV

TP11

TP9

TP5

TP8

TP10

198M1C

ISS M

TP

7

ZERO

ZERO

TP12

DISP

MPU active LED

(Flashing)

Fault LED

Sens V Test Point

TP7 + TP12

Sensor cell input

Sensor Volts

(RV3)

Zero

(RV2)

Span

(RV1)

4mA

(RV4)

Sensor Zeroing LEDs

CAN Transmitting LED

4-20mA  SInk/Source

4-20mA  Test

Jumper

End-of-line Jumper

Relay/Win Ribbon

LCD Contrast

Win Only

RS232

PC Data In/Out

Win Data Ribbon Cable

4-20op  Test Points

FIELD TERMINALS

HI      LO

24V Can+ Can- OV 4-20mA

24V Hi

Lo OV 4-20

mA

P

Y

W

Control Unit

CAN 1 or 2

Sensor

Addressable

+24  
Hi
Lo
0v
4~20mA

+24

Hi

Lo

0v

Control Unit

4~20mA Input

Sensor

3-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

EOL

T

FAULT

MPU

SK

SE

204M1C

ISS M

CONTRAST

Fault LED

Gas Type Header

Sensor cell input

20mA

Span

(RV2)

4mA

Zero

(RV1)

Sensor 4-20mA Routing Configurations

(see diagram)

CAN Transmitting LED

4-20mA  Test

Jumper

Relay/Win Ribbon

LCD Contrast

Win Only

End-of-line Jumper

+24V Test Point

(w.r.t 0V)

+24V

RS232

PC Data In/Out

Win Data Ribbon Cable

4-20mA  Test Pins

4-20mA  Sink Source

External 4-20mA  Input

(eg. Infrared)

+24V O/Pt

(eg. Infrared)

FIELD TERMINALS

HI      LO

24V Can+ Can- OV 4-20mA

24V Hi

Lo OV 4-20

mA

P

Y

W

Mainboad to Sensor wiring

Sensor Jumper configuration

Control Unit

CAN 1 or 2

Sensor

Addressable

+24  
Hi
Lo
0v
4~20mA

4~20 IN

SO

SK

+24

Hi

Lo

0v

Control Unit

4~20mA Input

Sensor

3-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

Control Unit

4~20mA Input

Sensor

2-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

Control Unit

CAN 1 or 2

Sensor

Addressable 4~20mA Input

+24  
Hi
Lo
0v
4~20mA

+24

Hi

Lo

0v

4~20 IN

SO

SK

4~20 IN

SO

SK

4~20 IN

SO

SK

ange

t magnets 

Command    

Use

A = Set CAN address  

Sets the CAN address 

G = Select gas type  

Select the gas type from a list 

Z = Zero  

Press when no gas on sensor to give zero 

S = Span  

Use when calibration gas applied, 

 

 

H and L change reading 

D = Enter calibration date  

Enter the calibration date

Y = Toggle auto zero  

Auto zero is ON or OFF, small drift is cleared

H = Set high alarm  

Sets the high alarm threshold 

L = Set low alarm  

Sets the low alarm threshold 

O = Set over range alarm  

Sets the over range alarm threshold 

P = List command  

List these commands on screen 

X = Exit calibration mode  

Exit this PC mode 

$ = Initialise this sensor  

Use on new PCB to set gas type to Flam 

U = Alarm direction  

Sets rising or falling alarms 

R = Range  

Allows a change in maximum value 

N = Decimal points     

Toggles between 1 and 2 decimal places

E = Edit user gas text  

Choose gas description

B = Toggle deadband  

Deadband of 2.5% can be on or off

F = Toggle fault Input   

External fault input contact can be disabled

# = Normally energised 

Low /high alarm relays and fault relay can be  

 

made normally energised

V= View gas log 

From current log, display how many historical  

 

readings to display, up to 2880

% = Clear gas log  

Set all 2880 log readings to 0.00

I = Log interval 

Choose how many seconds between each log  

 

reading and whether the log will roll over or  

 

stop at 2880 (60 second interval and 2880  

 

readings = 48 hours)

EOL

CAN

4-20

MPU

FAULT

TP1

OV

TP11

TP9

TP5

TP8

TP10

198M1C

ISS M

TP

7

ZERO

ZERO

TP12

DISP

MPU active LED

(Flashing)

Fault LED

Sens V Test Point

TP7 + TP12

Sensor cell input

Sensor Volts

(RV3)

Zero

(RV2)

Span

(RV1)

4mA

(RV4)

Sensor Zeroing LEDs

CAN Transmitting LED

4-20mA  SInk/Source

4-20mA  Test

Jumper

End-of-line Jumper

Relay/Win Ribbon

LCD Contrast

Win Only

RS232

PC Data In/Out

Win Data Ribbon Cable

4-20op  Test Points

FIELD TERMINALS

HI      LO

24V Can+ Can- OV 4-20mA

24V Hi

Lo OV 4-20

mA

P

Y

W

Control Unit

CAN 1 or 2

Sensor

Addressable

+24  
Hi
Lo
0v
4~20mA

+24

Hi

Lo

0v

Control Unit

4~20mA Input

Sensor

3-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

EOL

T

FAULT

MPU

SK

SE

204M1C

ISS M

CONTRAST

Fault LED

Gas Type Header

Sensor cell input

20mA

Span

(RV2)

4mA

Zero

(RV1)

Sensor 4-20mA Routing Configurations

(see diagram)

CAN Transmitting LED

4-20mA  Test

Jumper

Relay/Win Ribbon

LCD Contrast

Win Only

End-of-line Jumper

+24V Test Point

(w.r.t 0V)

+24V

RS232

PC Data In/Out

Win Data Ribbon Cable

4-20mA  Test Pins

4-20mA  Sink Source

External 4-20mA  Input

(eg. Infrared)

+24V O/Pt

(eg. Infrared)

FIELD TERMINALS

HI      LO

24V Can+ Can- OV 4-20mA

24V Hi

Lo OV 4-20

mA

P

Y

W

Mainboad to Sensor wiring

Sensor Jumper configuration

Control Unit

CAN 1 or 2

Sensor

Addressable

+24  
Hi
Lo
0v
4~20mA

4~20 IN

SO

SK

+24

Hi

Lo
0v

Control Unit

Addressable Sensor PCB

J10

+24V  
Hi
Lo
0v
4~20mA

4~20mA O/P Sensor

4~20mA

+24V 

0v

+24V 

0v

Sig

+24V

Hi

Lo
0v

J11

Control Unit

4~20mA Input

Sensor

3-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

Control Unit

4~20mA Input

Sensor

2-Wire Direct

4~20mA Signal

+24  
Hi
Lo
0v
4~20mA

+24

Sig

0v

4~20 IN

SO

SK

4~20 IN

SO

SK

204

Toxic

TP8

TP15

TP7

Display 

Contrast

Test

Addressable
Test Pins (mV)

Add

Vo

Direct test 

pins (mV)

4~20mA In (mV)

TP2
TP1

A

20mA

4mA

AG

Offset

Sensor

Comms 

Port

EOL

Field terminals

Relay PCB  
Connector

Display PCB  
Connector

4~20mA
24v DC
OV
FLT

IN

OUT
IN

Summary of Contents for 404+ Series

Page 1: ...GDS TECHNOLOGIES LTD FUSION POINT ASH LANE GARFORTH LEEDS LS25 2GA UK www gds technologies co uk This document is not contractual and the equipment specification may be modified at any time without prior notice C1795 Manual No 043D6C Issue Av2 GDS404 SERIES OPERATING HANDBOOK ...

Page 2: ...1 4 Alarm Board Component Layout 12 5 Sensor Termination 13 6 CV Transmitter Toxic Oxygen 14 7 CV Transmitter Flammable 15 8 XDI XDI win 30J Flammable Sensor 16 9 XDI XDI win 30J Toxic Oxygen Sensor 4 3 2 wire sensor 18 10 XDI XDI win 30J Prime Sensor 20 11 XDI XDI win 30J 4 20mA Input 22 SYSTEM DATA Manufacture date Works Order No Sensor type life life life life Gas Range Low alarm trip High alar...

Page 3: ...optional standby battery is fitted loss of mains supply will result in the GREEN Mains ON Lamp changing to RED GAS ALARM will be indicated by a red LED and display channel changing to a red background with text indicationg the alarm status Fault conditions are indicated by amber displays SOUNDER initiated in the presence of a fault or gas alarm condition TEST when pressed for 15 seconds alarm indi...

Page 4: ... CABLE Flammable catalytic 3 core 1 5mm screened cable mineral insulated copper sheathed or steel wire armoured maximum cable loop resistance 20 ohms Toxic Oxygen 3 core 0 5 mm screened cable mineral insulated copper sheathed or steel wire armoured maximum cable loop resistance 200 ohms POWER SUPPLY 230 110v AC 50 60Hz or 24v DC 21 30 volts tolerance POWER CONSUMPTION Per channel Normal operating ...

Page 5: ... As the gas rises it draws air from the surroundings and creates a turbulence Resulting from this there occurs rapid dilution and unless a sensor is positioned within the plume there will be no initial indication of a leak As gas continues to escape the diluted concentration rises to ceiling level and begins to layer In time the concentration at ceiling level will increase and this in turn will di...

Page 6: ...n the off condition Where an internal standby battery has been supplied the connectors should be made on JP11 and JP12 Re set alarms by pressing the reset button located on the front panel Allow ten minutes for the sensors to stabilise Any flammable or toxic sensors should be adjusted to read zero by means of appropriate ZERO POTENTIOMETER marked Z on the alarm module or for oxygen sensor adjust t...

Page 7: ...ters Over range alarm AL3 is set using the potentiometer on the front panel PCB labelled RL4 This is a global alarm that applies to all four channels One sensor zero level should be raised up to the desired alarm level by turning that channel s zero pot The Alarm 3 set pot should then be turned until the third alarm just activates default setting F S D The zero pot can then be adjusted back to nor...

Page 8: ...y down the procedure for dealing with a gas alarm or fault warning To ensure reliability an agreement should be negotiated for regular servicing When a service contract cannot be arranged an employee with suitable experience of electrical equipment should be trained to deal with the more simple servicing and instructed not to attempt to exceed the scope of such training Liaison should be establish...

Page 9: ...1 C2 C3 C4 INDICATORS L E L Lower Explosive Limit PPM Parts Per Million vol Volume Hi High Alarm Red Lo Low Alarm Red C1 C4 Channel Sensor Fault Indicator Amber Power On Green Mains Fail Red Inhibit Amber Reset Sounder Alarms Test Electronic System Test Fig 1 ACTION TO BE TAKEN IF THE APPARATUS ALARM SOUNDS A Extinguish all naked flames including all smoking materials B Turn off all gas appliances...

Page 10: ...1 TP5 DVM4 3V DVM4 5V DVM3 5V DVM2 5V DVM1 5V Option A Spare Jumpers Option B DVM3 3V DVM2 3V DVM1 3V DVM Lo Offset Alarm 3 set Fit to normally energise Fit to latch alarm NO C NC RL4 O R Relay OR Over range TP8 J22 TP10 TP2 TP7 SN1 TP6 0V 5V 3 3V J10 J26 J27 J30 J25 J26 S4 J1 USB Master Reset FSDA FClick J32 ...

Page 11: ...Normally energised Normally de energised J1 Global Alarm Relay Normally de energised Common Fault Relay Normally energised Normally de energised J5 Inhibit Relay Normally de energised Channel relays 1 4 A B Lo Hi see alarm board page 14 SOUNDER PERMANENT MUTE JP10 remove STANDBY BATTERY Connect leads to JP11 and JP12 ...

Page 12: ... Oxygen Alarm Set Low Low Alarm LL Time delay to alarm T1 10 secs T2 30 secs When used with GDS300 Flow sample systems FS SENSOR SELECTION 24v 4 20mA input P Pellistor mV input 4 20MA OUTPUT TP3 TP4 CALIBRATION TP1 TP2 ADJUSTMENTS Potentiometer RV1 Sensor Zero Potentiometer RV2 Sensor Calibration Potentiometer RV3 4 20mA signal output 4mA adjust Potentiometer RV4 4 20mA signal output 20mA adjust P...

Page 13: ... Unit Transmitter W Y P 24V OV SIG Sensor Sensor Sensor TOXIC SENSOR CELL OXYGEN P W Y P Y Fig 5 RED ident R flammable YELLOW ident Y toxic BLUE ident B oxygen GREEN ident G others W Y P W Y SIG P Fig 4 W Y P 24V Hi Lo Ov 4 20mA Panel W Y P 24V OV SIG Panel IR Transmitter W Y P 24V Hi Lo Ov 4 20mA W Y P W Y SIG P Panel 2 wire sensor Transmitter Panel Combi direct sensor Transmitter Panel Combi dir...

Page 14: ...here a digital panel meter is fitted to the CV card the reading may be adjusted by the DPM Z potentiometer zero Calibration With the digital meter connected to the test pins TP1 and TP2 and a reading of 4mV clean air apply test gas and wait until a maximum reading is obtained if necessary adjust the 20mA potentiometer for the required mV reading for the calibration gas being used Where 4 20mA span...

Page 15: ... printed on the CV circuit board 4 For oxygen level monitoring remove the sensor terminal connector from the PCB J4 or yellow wire and adjust the 4mA potentiometer for 4mA 4mV 5 Where a digital panel meter is fitted to the CV card the reading may be adjusted by the DPM Zero potentiometer Reconnect the cell and allow reading to stabilise adjust the DVM reading for 17 3mA 20 8 ambient oxygen using t...

Page 16: ...ate address is detected F indicates a fault present I shows that this sensor has its alarms inhibited under the O H L the v represent the direction of the alarms L is falling and H and O are rising A under the letter s OHLDFI represents a detected state so in this example the sensor would be in high alarm and a fault present Gas val 35 6 represents the value of the gas present at the sensor head P...

Page 17: ...r is 15 seconds approximately and is reset back each time a magnet is near Waiting till timeout is acceptable but this timeout can be speeded up by placing a magnet near to the centre position SPAN is the next part of the menu and gas should be applied to the sensor at this time The left magnet increases the gain and the right magnet reduces gain The actual sensor value can be seen on the display ...

Page 18: ... change the address of this sensor if required d Press N to select the number of decimal places to 1 or 2 ie dp 1 or dp 2 e With no gas applied and 4mV measured at test pins TP8 TP9 press Z to zero the gas reading see note f Then apply span gas and press S to enter span mode optain correct mV reading for test gas used by adjusting 20mA pot The displayed reading can be made HIGHER by pressing H or ...

Page 19: ...ay will return to normal after a few seconds timeout The right magnet allows the CAN address of the sensor to be changed WHEN the ADDRESS menu is displayed with a prompt to remove the magnet and then the display shows the address and that the right magnet will decreases it whilst the left magnet will increase it This is then stored in internal non volatile memory and the display will automatically...

Page 20: ...s that this sensor has its alarms inhibited under the O H L the v represent the direction of the alarms L is falling and H and O are rising A under the letter s OHLDFI represents a detected state so in this example the sensor would be in high alarm and a fault present Gas val 35 6 represents the value of the gas present at the sensor head Pressing R on the PC causes a reset to occur Gas type with ...

Page 21: ...eve a zero reading on the display A timer is displayed on the LCD and when this reaches 0 the next menu is displayed This timer is 15 seconds approximately and is reset back each time a magnet is near Waiting till timeout is acceptable but this timeout can be speeded up by placing a magnet near to the centre position SPAN is the next part of the menu and gas should be applied to the sensor at this...

Page 22: ...ssable 4 20mA Input 24 Hi Lo 0v 4 20mA 24 Hi Lo 0v 4 20 IN SO SK 4 20 IN SO SK 4 20 IN Command Use A Set CAN address Sets the CAN address G Select gas type Select the gas type from a list Z Zero Press when no gas on sensor to give zero S Span Use when calibration gas applied H and L change reading D Enter calibration date Enter the calibration date Y Toggle auto zero Auto zero is ON or OFF small d...

Page 23: ......

Page 24: ... T 44 0 113 286 0166 GDS TECHNOLOGIES LTD FUSION POINT ASH LANE GARFORTH LEEDS LS25 2GA UK www gds technologies co uk This document is not contractual and the equipment specification may be modified at any time without prior notice ...

Reviews: