7
Technical
CE Cert. No.
Ref
C
914
Sensor Points
One
Sensor Type
Catalytic, Electrochemical, Infra-red, Semiconductor
Measurements
Combustible gas – L.E.L. % vol.
Toxic gas PPM, % vol.
Oxygen - % vol. – depletion/enrichment
Refrigerant – ppm
Power Supply
Input - 230/115v AC – 50/60 Hz - 24v DC – Special 50v DC
Consumption
70W full alarm
Field Terminals
Screw Type – accepting up to 2.5 mm cable
Indicators
Gas level readout 3
1/2
digital display
Power – green L.E.D
Low alarm – red L.E.D
High alarm – red L.E.D
System fault – amber L.E.D
Flow fail – amber L.E.D - (Pump fail/line blockage)
User Interface
Panel mounted push buttons (two)
Reset – Mute sounder, reset alarms, initiate alarm relay inhibit
Test – check alarm indicators, sounder and relay action
Alarm Settings
Digital setting (fully adjustable between zero and full scale)
Normally latched – option auto reset
Outputs
Relay – high level gas alarm S.P.C.O.
Relay – low level gas alarm S.P.C.O.
Relay – system fault S.P.C.O.
Relay – flow fail S.P.C.O. – flow fail alarm board
All contacts rated 5A 230v AC
All relay contacts used to switch inductive loads (relays etc)
should have suppressors fitted, typical device Farnell 772-756
4~20mA analogue output or 1~5v
Optional data logger
24v DC @ 100mA - Available for auxiliary equipment
Audible Alarm
Lo, hi, fault flow fail alarms 98dB @ 38cm
Dimensions
H 265mm x W 315mm x D 75mm
Cable Entry
Base – Rear
Weight
3.7 kg