202105
87
P
ar
t 2
-
O
u
td
o
o
r
U
n
its
CHV Mini VRF 50/60Hz
Combination (%)
(Capacity index)
Outdoor Air
temperature
Indoor temperature(
°
C DB)
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°
C DB
°
C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-15.0
-16.5
8.2
2.64
8.1
2.67
7.9
2.70
7.8
2.75
7.6
2.81
7.2
2.95
-13.7
-15.0
8.5
2.67
8.3
2.70
8.2
2.72
8.0
2.78
7.8
2.83
7.5
2.98
-11.8
-13.0
8.8
2.70
8.6
2.72
8.4
2.75
8.3
2.81
8.1
2.86
7.7
3.01
-9.8
-11.0
9.0
2.72
8.9
2.75
8.7
2.78
8.5
2.83
8.3
2.89
7.9
3.04
-9.5
-10.0
9.3
2.75
9.1
2.78
8.9
2.81
8.8
2.86
8.6
2.92
8.2
3.07
-8.5
-9.1
9.6
2.78
9.4
2.81
9.2
2.84
9.0
2.89
8.9
2.95
8.4
3.10
-7.0
-7.6
9.9
2.81
9.7
2.84
9.5
2.86
9.3
2.92
9.1
2.98
8.7
3.13
-5.0
-5.6
10.2
2.84
10.0
2.86
9.8
2.89
9.6
2.95
9.4
3.01
8.9
3.16
-3.0
-3.7
10.5
2.86
10.3
2.89
10.1
2.92
9.9
2.98
9.7
3.04
9.2
3.19
0.0
-0.7
11.1
2.92
10.9
2.95
10.6
2.98
10.4
3.04
10.2
3.10
9.7
3.26
3.0
2.2
11.7
2.98
11.4
3.01
11.2
3.04
11.0
3.10
10.8
3.17
10.2
3.32
5.0
4.1
12.3
3.04
12.0
3.07
11.8
3.10
11.6
3.17
11.3
3.23
10.8
3.39
7.0
6.0
12.9
3.10
12.7
3.14
12.4
3.17
12.2
3.23
11.9
3.30
11.3
3.46
9.0
7.9
13.2
3.14
12.9
3.17
12.7
3.20
12.4
3.26
12.2
3.33
11.5
3.50
11.0
9.8
13.4
3.17
13.2
3.20
12.9
3.23
12.7
3.30
12.4
3.36
11.8
3.53
13.0
11.8
13.7
3.20
13.4
3.23
13.2
3.26
12.9
3.33
12.6
3.40
12.0
3.57
15.0
13.7
14.0
3.23
13.7
3.26
13.4
3.30
13.2
3.36
12.9
3.43
12.3
3.60
60%
-15.0
-16.5
7.2
2.31
7.1
2.34
6.9
2.36
6.8
2.41
6.7
2.45
6.3
2.58
-13.7
-15.0
7.4
2.34
7.3
2.36
7.2
2.38
7.0
2.43
6.9
2.48
6.5
2.60
-11.8
-13.0
7.7
2.36
7.5
2.38
7.4
2.41
7.2
2.46
7.1
2.50
6.7
2.63
-9.8
-11.0
7.9
2.38
7.8
2.41
7.6
2.43
7.5
2.48
7.3
2.53
6.9
2.66
-9.5
-10.0
8.2
2.41
8.0
2.43
7.8
2.46
7.7
2.51
7.5
2.56
7.2
2.68
-8.5
-9.1
8.4
2.43
8.2
2.46
8.1
2.48
7.9
2.53
7.8
2.58
7.4
2.71
-7.0
-7.6
8.7
2.46
8.5
2.48
8.3
2.51
8.2
2.56
8.0
2.61
7.6
2.74
-5.0
-5.6
8.9
2.48
8.8
2.51
8.6
2.53
8.4
2.58
8.3
2.63
7.8
2.77
-3.0
-3.7
9.2
2.51
9.0
2.53
8.9
2.56
8.7
2.61
8.5
2.66
8.1
2.79
0.0
-0.7
9.7
2.56
9.5
2.58
9.3
2.61
9.1
2.66
9.0
2.71
8.5
2.85
3.0
2.2
10.2
2.61
10.0
2.64
9.8
2.66
9.6
2.72
9.4
2.77
9.0
2.91
5.0
4.1
10.8
2.66
10.5
2.69
10.3
2.72
10.1
2.77
9.9
2.83
9.4
2.97
7.0
6.0
11.3
2.72
11.1
2.74
10.9
2.77
10.7
2.83
10.4
2.88
9.9
3.03
9.0
7.9
11.5
2.74
11.3
2.77
11.1
2.80
10.9
2.86
10.7
2.91
10.1
3.06
11.0
9.8
11.8
2.77
11.5
2.80
11.3
2.83
11.1
2.88
10.9
2.94
10.3
3.09
13.0
11.8
12.0
2.80
11.8
2.83
11.5
2.86
11.3
2.91
11.1
2.97
10.5
3.12
15.0
13.7
12.3
2.83
12.0
2.86
11.8
2.88
11.5
2.94
11.3
3.00
10.7
3.15
50%
-15.0
-16.5
6.2
1.98
6.1
2.00
6.0
2.02
5.8
2.06
5.7
2.10
5.4
2.21
-13.7
-15.0
6.4
2.00
6.3
2.02
6.2
2.04
6.0
2.08
5.9
2.13
5.6
2.23
-11.8
-13.0
6.6
2.02
6.5
2.04
6.3
2.06
6.2
2.10
6.1
2.15
5.8
2.25
-9.8
-11.0
6.8
2.04
6.7
2.06
6.5
2.08
6.4
2.13
6.3
2.17
6.0
2.28
-9.5
-10.0
7.0
2.06
6.9
2.08
6.7
2.11
6.6
2.15
6.5
2.19
6.2
2.30
-8.5
-9.1
7.2
2.08
7.1
2.11
7.0
2.13
6.8
2.17
6.7
2.21
6.3
2.32
-7.0
-7.6
7.5
2.11
7.3
2.13
7.2
2.15
7.0
2.19
6.9
2.23
6.5
2.35
-5.0
-5.6
7.7
2.13
7.5
2.15
7.4
2.17
7.2
2.21
7.1
2.26
6.7
2.37
-3.0
-3.7
7.9
2.15
7.8
2.17
7.6
2.19
7.5
2.24
7.3
2.28
6.9
2.39
0.0
-0.7
8.3
2.19
8.2
2.21
8.0
2.24
7.9
2.28
7.7
2.33
7.3
2.44
3.0
2.2
8.8
2.24
8.6
2.26
8.4
2.28
8.3
2.33
8.1
2.37
7.7
2.49
5.0
4.1
9.2
2.28
9.1
2.31
8.9
2.33
8.7
2.38
8.5
2.42
8.1
2.54
7.0
6.0
9.7
2.33
9.5
2.35
9.4
2.38
9.2
2.42
9.0
2.47
8.5
2.60
9.0
7.9
9.9
2.35
9.7
2.38
9.5
2.40
9.3
2.45
9.2
2.50
8.7
2.62
11.0
9.8
10.1
2.38
9.9
2.40
9.7
2.42
9.5
2.47
9.3
2.52
8.9
2.65
13.0
11.8
10.3
2.40
10.1
2.42
9.9
2.45
9.7
2.50
9.5
2.55
9.1
2.67
15.0
13.7
10.5
2.42
10.3
2.45
10.1
2.47
9.9
2.52
9.7
2.57
9.2
2.70
Note:
1.
is tested under our standard condition.
2. In heating mode, avoid running the unit when the outdoor air temperature is below -15 degrees.
3. The above table shows the average value of conditions may operate.
Summary of Contents for CHV Mini Series
Page 1: ...Commercial AirConditioners Service Manual R410A Series...
Page 3: ...CHV Mini VRF 50 60Hz 2 202105 CHV Mini Series ServiceManual...
Page 13: ...CHV Mini VRF 50 60Hz 12 202105 CHV Mini Series ServiceManual...
Page 109: ...108 202105 CHV Mini Series ServiceManual CHV Mini VRF 50 60Hz 1 ExplodedViews...