Page 3
Thank you for purchasing an A2000 Series water heater/boiler from Green Boiler Technologies. Your model
was proudly built in the United States with high quality components and craftsmanship. With the proper
installation and maintenance, your A2000 heater/boiler will provide years of outstanding performance.
The A2000 series water heaters and water boilers utilize efficient copper fin-tube heat exchangers and are
certified as Category I Appliances. Category I equipment utilizes natural draft to remove flue gases without need
of a fan or draft inducer, and has flue gas temperatures more than 140° F above the dew point.
The unique design of the appliance provides excellent heat transfer and a small footprint. The heat exchanger
resists build-up of lime scale and allows de-liming without disassembly of the unit.
DIMENSIONS & SPECIFICATIONS
Model
A
B
C
D
E
F
G
H
K
A2-035
7
17 ½
34 ½
38
58
9
24
10
29
A2-050
8
16 ½
33
42
69
10
28
18 ½
33
A2-070
10 ¼ 13 ¼
33
38 ¾
66
12
32
25
36 ¼
A2-097
6 ¾
17 ¾
38
41 ¼
77 ¼
16
35
20
43
A2-120
7
17 ½
44 ½
48 ½
84 ½
16
35
22
43
A2-140
7
17 ½
44 ½
48 ½
100 ½
18
35
22
43
Dimensions in Inches; Dimensions For Units With Standard Gas Train
Model
BTU
Input
**
GPH @
100
o
Rise
Gas
Connection
Water
Connection
Vent
Diameter
Shipping
Weight
*
A2-035
350,000
336
1
1 ½
9
460
A2-050
500,000
480
1
1 ½
10
600
A2-070
700,000
672
1 ¼
1 ½
12
650
A2-097
970,000
932
1 ¼
1 ½
16
700
A2-120
1,200,000
1152
1 ½
1 ½
16
804
A2-140
1,400,000
1345
1 ½
1 ½
18
944
Dimensions In Inches; GPH = Gallons Per Hour; * Approximate
**
Propane Model Input Is 10% Less
INTRODUCTION
Summary of Contents for A2-035
Page 30: ...Page 29 DIAGRAMS...
Page 31: ...Page 30...
Page 33: ...Page 32 WIRING DIAGRAM A2000 Water Heater Models...
Page 34: ...Page 33 WIRING DIAGRAM A2000 Boiler Models...
Page 35: ...Page 34 WIRING DIAGRAM A2000 CSD 1 Boiler Models...
Page 36: ...Page 35 A2000 WITH CONSTANT PUMP OPERATION A2000 WITH ON OFF PUMP OPERATION...
Page 37: ...Page 36 A2000 WITH INFITEC PUMP DELAY...
Page 44: ......