background image

MAINTENANCE AND CLEANING INSTRUCTIONS

At the end of each cooking day, the exposed interior surfaces of the hood 
should be wiped down and the grease cup emptied. During the course of 
operation, grease particles are gradually collecting inside the cartridge 
extractors. Daily, or at periodic intervals, depending on the type of cook

-

ing, the cartridge extractors must be removed and cleaned.  To clean, 
proceed as follows:
1.    Remove filters.  CAUTION:  Care should be taken when removing 

filters, especially over fryers.  It is recommended that the cooking 
equipment be cooled down and the fryers be covered prior to removing 
filters.  To remove, lift up slightly on filters and pull out at the bottom, 
then straight down.

2.    Filters may be cleaned either by using a dishwasher or by soaking in 

deep well sink using hot water with a degreasing detergent, scrubbed 
and rinsed.  Prior to cleaning, open the XG extractor to gain access 
to the filters interior. Formula G-510  is highly recommended for this 
application.  For information contact:

20/10 Products
P.O. Box 7609
Salem, Oregon 97303  
Phone: 800-286-2010
Fax:  503-363-4296
email: [email protected]

3.    With extractors removed, wipe and clean the back wall and top of the 

plenum area and the grease gutter with hot detergent water.  NOTE:  If 
steam or hot water pressure wash is used for periodic cleaning of the 
interior, remove the grease drawer and connect a hose to the gutter 
drain and lead it to a floor sink or large bucket to drain off water.

4.    Replace extractors.  Be sure to replace extractors with baffles running 

vertical as shown in Fig. 5.

IMPORTANT NOTE:  In the event of a fire the thermostat must be replaced. 
(Applicable to GFBD models only.)

3

FIGURE 4

FIGURE 5

NOTE: NEVER OPERATE THE HOOD 
IF THE FILTERS ARE NOT IN PLACE.

NOTE:  EXTRACTORS  MUST  BE  INSTALLED WITH 
BAFFLES RUNNING VERTICAL AS SHOWN.

CAUTION: Care should be taken when removing 
extractors, especially over fryers.  It is recommend

-

ed that the cooking equipment be cooled down and 
the fryers be covered prior to removing filters.

INSPECTION AND CLEANING REQUIREMENTS

The 1998 edition of NFPA-96 (Standard for Ventilation Control and Fire 

Protection of Commercial Cooking Operations)  require that hoods, ducts 

and exhaust fans be inspected by a properly trained, qualified and certified 

company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from grease-

laden vapors, the entire exhaust system shall be cleaned by a properly 

trained, qualified, and certified company or person(s) acceptable to the 

authority having jurisdiction in accordance.
When a vent cleaning service is used, a certificate showing date of in

-

spection or cleaning shall be maintained on the premises.  After cleaning 

is completed, the vent cleaning contractor shall place or display within 

the kitchen area a label indicating the date cleaned and the name of the 

servicing company.  It shall also indicate areas not cleaned.

Factory  trained  service  agencies  are  cer tified  by  Gaylord 

 

Industries  to  perform  these  inspections.      For  the  name  and  phone 

number of your nearest agent, call 1-800-547-9696 or send an e-mail to          
[email protected].

FIGURE 6

E

L

U

D

E

H

C

S

N

O

I

T

C

E

P

S

N

I

M

E

T

S

Y

S

T

S

U

A

H

X

E

s

n

o

it

a

r

e

p

o

g

n

i

k

o

o

c

l

e

u

f

d

il

o

s

g

n

i

v

r

e

s

s

m

e

t

s

y

S

y

l

h

t

n

o

M

s

n

o

it

a

r

e

p

o

g

n

i

k

o

o

c

e

m

u

l

o

v

-

h

g

i

h

g

n

i

v

r

e

s

s

m

e

t

s

y

s

k

o

w

r

o

g

n

il

i

o

r

b

r

a

h

c

,

g

n

i

k

o

o

c

r

u

o

h

-

4

2

s

a

h

c

u

s

g

n

i

k

o

o

c

y

lr

e

t

r

a

u

Q

g

n

i

k

o

o

c

e

m

u

l

o

v

-

e

t

a

r

e

d

o

m

g

n

i

v

r

e

s

s

m

e

t

s

y

s

s

n

o

it

a

r

e

p

o

y

ll

a

u

n

n

a

-

i

m

e

s

,

s

n

o

it

a

r

e

p

o

g

n

i

k

o

o

c

e

m

u

l

o

v

-

w

o

l

g

n

i

v

r

e

s

s

m

e

t

s

y

s

l

a

n

o

s

a

e

s

,

s

p

m

a

c

y

a

d

,

s

e

h

c

r

u

h

c

s

a

h

c

u

s

s

r

e

t

n

e

c

r

o

i

n

e

s

r

o

,

s

e

s

s

e

n

i

s

u

b

y

ll

a

u

n

n

a

NOTE: FILTERS SHOULD BE OPENED PRIOR TO 
CLEANING.

Summary of Contents for XG SERIES

Page 1: ...LLATION OPERATION MAINTENANCE MANUAL for XG SERIES HOODS 10900 S W AVERY STREET TUALATIN OREGON 97062 U S A 1 800 547 9696 503 691 2010 FAX 503 692 6048 email info gaylordusa com GAYLORD INDUSTRIES EFFECTIVE DATE 5 2008 ...

Page 2: ...dling Equipment etc please refer to the corresponding supplementary equipment manuals If you have further questions please call us toll free at 1 800 547 9696 We are more than happy to help Sincerely Gaylord Industries Street Address 10900 S W Avery Street Tualatin Oregon 97062 8549 U S A PHONE 503 691 2010 800 547 9696 FAX 503 692 6048 email gaylord gaylordusa com www gaylordusa com GAYLORD INDUS...

Page 3: ...0 The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials ALL RIGHTS RESERVED NO PART OF THIS BOOK MAY BE REPRODUCED STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM BY AN ELECTRIC ME CHANICAL PHOTOCOPYING RECORDING MEANS OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION OF GAY...

Page 4: ...ways have access to the inside of the extractors for easy cleaning and will not mistakenly install the units in the opened or disassemble position CLEANING At the end of the cooking day or at periodic intervals cartridges are removed and washed either in a dishwasher or soaked in a deep well sink scrubbed and rinsed FIRE PROTECTION NFPA 96 requires the use of surface duct and plenum pro tection on...

Page 5: ...Gaylord Fire Balancing Damper Has a thermostatically activated electric Fire Balancing damper located at the duct collar Can be used in the horizontal position ND No Damper 3 Style BDL Wall canopy style BDL CL Island style for single line of cooking equipment using one extraction chamber Light Medium Duty BDL DS CL Island style for single line of cooking equipment using one extraction chamber Ligh...

Page 6: ...are should be taken when removing extractors especially over fryers It is recommend ed that the cooking equipment be cooled down and the fryers be covered prior to removing filters INSPECTION AND CLEANING REQUIREMENTS The 1998 edition of NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations require that hoods ducts and exhaust fans be inspected by a properly...

Page 7: ...r h t e h t r a e n d e t a c o l s r e t s i g e r r i a p u e k a M o t d e t s u j d a e b d l u o h s s r e v u o l e h t d o o h d o o h e h t m o r f y a w a r i a e h t t c e r i d e h t t a r i a p u e k a m g n i c r o f r o g n i t c e r i D s t f a r d s s o r c s e t a e r c y l l a c i p y t d o o h s s o l e k o m s n i g n i t l u s e r r o f d e i l p p u s e b t s u m r i a p u e ...

Page 8: ...m n e e b e v a h y a m h c t i w s r o t c e l e s n o i t i s o p c i t a m o t u a e h t m o r f d e p p i r t r e k a e r b t i u c r i c n a f t s u a h x E d e s u f a h t i w d e p p i u q e s i m e t s y s e h t f I a n a f t s u a h x e e h t r o f h c t i w s t c e n n o c s i d t u o n w o l b e v a h y a m s e s u f r o e s u f d e r i w n e e b t o n s a h h c t i w s f f o n o n a F ...

Page 9: ...termine your rate of flow for the hood per unit length of the hood Total flow will be the CFM LF obtained from Fig 9 multiplied by the length of the ventilator section 8 Design values will be noted on the listing label attached to the inside of the ventilator or sticker attached to the inside of the access cover Fig 9 Airflow vs Static Tap Chart Balancing Hood system flow rates are to be adjusted ...

Page 10: ...18400 Extractor Removal Tool For 250 400 CFM Lin Ft Extractors Kason INCANDESCENT LIGHT LENS FRAME 12 x 12 Recessed Light Lens Retainer FLUORESCENT LIGHT LENS FRAME 2 Ft Recessed Light Lens Retainer 3 Ft Recessed Light Lens Retainer 4 Ft Recessed Light Lens Retainer 13211 13210 10111 10112 19872 EXHAUST DUCT THERMOSTATS 6 NC 325 F 19176 Damper Control Motor 24 volt For GFBD Model Dampers Control G...

Page 11: ...Manual 7 Hoods are constructed of 18 Ga stainless steel Type 304 No 4 finish unless otherwise noted on drawings AIR FLOW RATES 8 The exhaust air flow rates and supply if part of the hood must be set at the rate stamped on the hood nameplate The exhaust volumes and supply when provided were established under controlled laboratory conditions and greater exhaust and or lesser supply may be required f...

Page 12: ...rox 1 minute 15 seconds _____Yes ___No B The exhaust fan came on ___Yes ___No 2 Turn off the exhaust fan A The damper should move to the fully closed position in approx 15 seconds_____Yes_____No B The exhaust fan shut off ___Yes ___No INSTALLATION INCLUDES THE FOLLOWING Gaylord Auto Start Controller Gaylord Clearair Pollution Control Unit RSPC The Gaylord Quencher Fire Protection System Gaylord Di...

Page 13: ...CH OF THIS WARRANTY In the United States the labor required to make repairs and replacements under this warranty shall be furnished by Gaylord Industries or the Licensed Gaylord Manufacturer or its authorized representative Such labor shall only be provided Mondays through Fridays between the hours of 8 a m and 4 p m Re quests for repairs or replacement parts should be made to GAYLORD INDUSTRIES 1...

Page 14: ...est certified service agency call or write to gaylord industries FORM NO TM XG 0508 COPYRIGHT 2008 GAYLORD INDUSTRIES LITHO IN U S A 10900 s w avery street tualatin oregon 97062 u s a Call 503 691 2010 1 800 547 9696 Fax 503 692 6048 email info gaylordusa com local service agency ...

Reviews: