RG66000889-REV.OO 14
Fan
Type
Min.
Max.
M.U.
Var.
Galletti
Def.
Presence
F7
- Temperature value for min Winter
speed
- Pressure value for min Winter speed
U F8
F8
F8
50
122
/5
°C
°F
bar
0.1
0.1
0
0
-V-S-
F8
- Temperature value for max Winter
speed
- Pressure value for max Winter speed
U 0
32
/4
F7
F7
F7
°C
°F
bar
0.1
0.1
0
0
-V-S-
F9
- Temp. to turn OFF the fan in Summer
- Pressure to turn OFF the fan in
Summer
U 0
32
/4
F5
F5
F5
°C
°F
bar
0.1
0.1
0
0
-V-S-
FA
- Temp. to turn OFF the fan in Winter
- Pressure to turn OFF the fan in Winter
U F7
F7
F7
50
122
/5
°C
°F
bar
0.1
0.1
0
0
-V-S-
Fb
Starting time of fans
U
0
15
4 sec
1
0
-V-S-
Regulator
Type
Min.
Max
M.U.
Variation
Galletti
Default
Presence
d1 Defrosting
cycle
/Condensation
antifreeze
0=no 1=yes
U 0 1 flag
1
0 ---S-
d2 Time-or temperature-based
defrosting0=time1=temperature
U 0 1 flag
1
0 D--S-
d3
- Start defrosting temperature
- Condensation antifreeze alarm set
point
- Start defrosting pressure
U -30
-22
/4
d4
d4
d4
°C
°F
bar
0.1
0.1
0
0
D--S-
d4
- End-defrosting temperature
- End-defrosting pressure
U d3
d3
d3
50
122
/5
°C
°F
bar
0.1
0.1
0
0
D--S-
d5
Min. time-interval to start a defrosting
cycle
U 10
150
sec
10
0 D--S-
d6
Min. duration of a defrosting cycle
U
0
150
sec
10
0
D--S-
d7
Max. duration of a defrosting cycle
U
1
15
min
1
0
D--S-
d8
Time-delay between 2 defrosting
cycles within the same circuit
U 10
150
min
10
0 D--S-
d9
Defrosting time-interval between the
2 circuits
U 0 150
min
10
0 D--SB
dA
Defrost end by external contact F 0 1 flag
1
0 D--S-
db
Antifreeze heaters activated while
defrosting
U 0 1 flag
1
0 D--S-
dc
Delay before defrosting
F
0
3
min
1
0
D--S-
dd
Delay after defrosting
F
0
3
min
1
0
D--S-
dE
End defrosting with 2 refrigerating
circuits and 1 removal fan
F 0 1 flag
1
0 D--SB
Antifreeze
Type
Min.
Max
M.U.
Variation
Galletti
Def.
Presence
A1 Antifreeze
U
-30
-22
A4
A4
°C
°F
0.1 4.0 -----
A2
Differential for antifreeze
U
0.1
0.1
11.0
19.8
°C
°F
0.1 2.0 -----
A3
Bypass time for antifreeze alarm
U
0
150
sec
10
10
-----
A4
Set point for the activation of antifreeze
heater
U A1
rd °C/°F
0.1
0
-----
A5
Diff. for antifreeze heater
U
0.1
11.0
°C
0.1
0
-----