www.gastron.com
18
_
19
GTC-200F
Instruction Manual
6. Installation
6. Installation
6.3. Configuration of channel Unit terminals
[Figure 7. Configuration of
Channel Unit terminal]
NO
TERMINAL CONFIGURATION
DESCRIPTION
1
Output 4-20mA +
4-20mA output of measure values of detection unit
2
Output 4-20mA -
3
TROUBLE RELAY NO
Output Relay for breakdown state
4
TROUBLE RELAY NC
5
TROUBLE RELAY COM
6
Alarm3 RELAY NO
Output Relay for 3rd alarm
7
Alarm3 RELAY NC
8
Alarm3 RELAY COM
9
Alarm2 RELAY NO
Output Relay for 2nd alarm
10
Alarm2 RELAY NC
11
Alarm2 RELAY COM
12
Alarm1 RELAY NO
Output Relay for 1st alarm
13
Alarm1 RELAY NC
14
Alarm1 RELAY COM
15
Power supply for de
Supply power to detection unit and
input 4-20mA signals
16
4-20mA input for detector
17
Power supply for detector -
6.4. Connection method of 3-wire type for Gas detector
■ When the gas detector is configured with power supply and 4-20mA output using 3 wires(V+, mA, V- ),
connect to the channel unit by the following method.
■ Connection cable should be configured with shield cable of CVVS or CVVSB of more than1.5sq.
[Figure 8. 3-wire connection method for gas detector]
■ Our company's detector models of the relevant method include TS-1100Ex, TS-2000Ex, TS-2100 Series,
TS-4000 Series, TS-4100P Series, TS-5100 Series, GTD-1000 Series, GTD-2000 Series, GTD-3000 Series,
and GIR-3000 Series.
6.5. Connection method of 2-wire type for Gas detector
■ When output of gas detector is configured using 2-wires(V+, V- ), connect to the channel unit by the following method.
■ nection cable should be configured with shield cable of CVVS or CVVSB of more than1.5sq.
■ Our company's detector models of the relevant method include TS-1100Tx, TS-2000Tx, TS-3000 Series, and
TS-3100 Series.
[Figure 9. 2-wire connection method for gas detector]