![GasTech F-Guard-IR3-H2 User Manual Download Page 34](http://html.mh-extra.com/html/gastech/f-guard-ir3-h2/f-guard-ir3-h2_user-manual_568654034.webp)
For more information & technical support:
29
F-Guard IR3-H2 User Manual
76-M-6010-02-02
9
Specifications
Fire Detection
•
Detection time and distance:
o
40ms
-
for fast fire burst or explosion
o
1.5s
-
for
32″ (0.8m) hydrogen fire at 0
–66ft. (0–20m)
o
4s
-
for
32″ (0.8m) hydrogen fire at 66
–100ft. (20–30m)
•
Field of view: 90° Horizontal, 75° Vertical
•
Time Delay: 0-30 seconds (adjustable)
•
Built-in test: Automatic and Manual
Electrical Specifications
•
Operating Voltage: 24 VDC nominal (18-32 VDC)
•
Current Consumption:
o
Standby
120mA
o
Maximum
180mA all systems in operation (including window heater)
•
Cable Entries: 2x conduit entries 3/4” NPT or M25, with one entry plugged with a suitably
certified stopper.
•
Wiring: 14 to 17 AWG (2.5mm
2
to 1.0mm
2
)