Gasolec G12 Instruction Manual Download Page 5

 

 

Gameco 

 

G12 

 

 

Installation 

Installation of the G12 heater should be undertaken by an authorised person in accordance 
with Australian standard AS5601 Gas Installations and must also comply with local and 
statutory and regulatory requirements. 
The heater is to be mounted in an area with adequate ventilation. Ventilation requirements 
must be in accordance with AS5601. Gas Installations and must also comply with local 
statutory and regulatory requirements. 

The gas piping system for heaters using LPG must have an approved gas regulator fitted to 
give a supply pressure to the heater inlet of 2.75 kPa. Use the pressure tapping point located 
at the gas inlet on the Maxitrol valve to check inlet pressure. 

The gas piping system for heaters using NG must have an approved appliance gas regulator 
fitted to give a supply pressure to the heater inlet of 1.00 kPa. Use the pressure tapping 
point on the appliance regulator to check the inlet pressure. 
 
A 3m long hose certified to AS/NZS 1869 Class C is supplied and must be used to connect 
the heater to the gas supply. The hose shall be installed to ensure it is not exposed to 
excessive radiant heat and placed so there is no undue strain on the hose during operation. 
 
Installation Height from floor: 

 

1.5 -1.7 meter  to bottom of reflector 

                

Air gap above heater 

 

 

   1.0   meter minimum overhead clearance 

Distance to any combustible product:         1.5    meter minimum 

1.  Before burner ignition, ensure that gas is present at the burner inlet and check that 

all gas connections are gas tight and there are no leaks. Use a soapy water 
mixture or other approved leak check solution to ensure all fittings are sealed. Any 
tell tale bubbles will mean the joint is not sealed; undo the joint, check the sealing 
faces and threads for damage. Reseal and recheck for tightness. Ensure the soap 
solution does not contain any traces of AMMONIA in the mixture. Ammonia can 
have a detrimental effect on the brass joint. 

2.  Check the hose is not kinked or damaged. 
3. The temperature sensing bulb on the G12-TM model should be swivelled down 

toward the floor to allow the bulb to sense air temperature away from the heater. 

4.  On completion of installation the heater must be tested and commissioned. 
 

Lighting 

Model G12-TM 

1. Slide pilot cover open or off to expose pilot burner. (Fig1) 
2. Push in and turn the control knob on the thermostat to PILOT, this releases gas to 
    the pilot burner. (Fig 3) 
3. While holding the control in, light the pilot burner (Fig2). The pilot flame should   
    play onto the tip of the thermocouple.  
    After 5-10 seconds, release the pilot button, the pilot flame should remain alight.  
    Check that the pilot flame is stable, refit the pilot cover and slide closed. 
4. Turn the Control Knob to ON position, and turn the numbered dial to position 7,     
     this will release gas to the burner. 
5.  The main gas will ignite smoothly from the pilot flame, the flame should be blue in  
     colour with no yellow flame present. The flame will establish and start to warm   
     the heat emitter. After a while the heater will come up to temperature, and the  
     emitter will glow red. 

Summary of Contents for G12

Page 1: ...amatta Road AUBURN NSW 2144 Phone 02 96485856 Email martynt gameco com au GAMECO Victoria 65A Chifley Drive PRESTON VIC 3072 Phone 03 94803633 GAMECO QUEENSLAND 17 Roy Street MILTON QLD 4064 Phone 07 33777999 GAMECO NEW ZEALAND LTD 9 Villa Street Masterton NZ Phone 06 3701683 ...

Page 2: ...which has developed under normal installation use and service GAMECO GASOLEC assumes no responsibility for the costs of removal and installation of the product or other incidental costs which may arise as a result of any defects in materials or workmanship This is an overview of Gameco s sole warranty with respect to the products delivered hereunder No statement representation agreement or underst...

Page 3: ...e should never be above or below a heater and positioned to minimise radiant heat affects TO BE INSTALLED ONLY BY AN AUTHORISED PERSON DO NOT PLACE ARTICLES ON OR AGAINST THIS APPLIANCE DO NOT USE OR STORE FLAMMABLE MATERIALS NEAR THIS APPLIANCE DO NOT SPRAY AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHILE IT IS IN OPERATION ...

Page 4: ...th stand alone thermostat control G12TSLP With 24AC 12v DC solenoid valve control For use with Natural Gas G12 TM NG With stand alone thermostat control Gas rating 45 Mj hr Gas Connection The gas connection is located on the gas control valve For ULPG 3 8 BSP male connection For natural gas BSP male connection The heater has a circular reflector with a diameter of 570mm Giving a circular heating p...

Page 5: ...e that gas is present at the burner inlet and check that all gas connections are gas tight and there are no leaks Use a soapy water mixture or other approved leak check solution to ensure all fittings are sealed Any tell tale bubbles will mean the joint is not sealed undo the joint check the sealing faces and threads for damage Reseal and recheck for tightness Ensure the soap solution does not con...

Page 6: ...onto the tip of the thermocouple After 5 10 seconds release the button and the pilot flame should remain alight After checking that the flame is stable refit and slide the pilot cover closed 4 Set the shed controller to the desired temperature 5 The controller will signal the solenoid valve on the heater to open and put gas to the heater The gas will ignite smoothly from the pilot flame the flame ...

Page 7: ...rson once a year Trouble shooting 1 If the gas flame is soft and yellow refer to previous section on heater maintenance 2 If the pilot fails to light first check to see that gas is present at the inlet and is at the correct pressure 3 Check that the pilot orifice is clear clean or replace if blocked 4 If the pilot light does not remain lit after releasing the control button check that the pilot fl...

Page 8: ... all gas pipe and gas hose connections for leaks with soap and water solution or other leak check solution See Installation section 1 NEVER check for leaks with an naked flame 5 Ventilation air and combustion air must not be obstructed 6 Do not adjust the height maintain or repair the heater while it is still hot 7 Never bypass any safety devices 8 Do not operate a heater if you suspect there are ...