![Gascat DOMUS HF Installation & Operation Manual Download Page 6](http://html1.mh-extra.com/html/gascat/domus-hf/domus-hf_installation-and-operation-manual_3659988006.webp)
Installation and Operation Manual
Domus HF - Pressure Regulating Valve
MI-23
Elaborado
Verificado / Aprovado
CSQ
Data
Revisão
Página
JJ
VBL
JM
15/12/17
00
6 de 19
2.3.3 – TEMPERATURE LIMITS
Operating temperature: -20°C a 60°C
Ambient temperature: -20°C a 60°C
The temperature limits informed at this manual or in any applicable standard must not be exceeded under any
circumstances, at risk of damage the equipment, safety of installation and safety of people involved in the operation.
2.3.4 – FLOW COEFICIENT
DN
KG
1”
200
2”
600
2.3.5 – VALVE WEIGHT
DN
150# / PN16 / NPT-F
1”
28 Kg
2”
38 Kg
2.3.6 – MAXIMUM WORKING PRESSURE
600#
103 bar
The pressure limit informed at this manual or in any applicable standard must not be exceeded under any
circumstances, at risk of damage the equipment, safety of installation and safety of people involved in the operation.
2.3.7 – PRESSURE REGULATOR SPRING RANGE (SET-POINT)
PILOT G31F
SPRING COLOR
PART NUMBER
RANGE
SILVER
01.49.61
0.7 – 2.8 bar
GREEN
01.49.65
2.0 – 5.0 bar
RED
01.49.64
4.5 – 14.0 bar
BROWN
01.49.33
7 – 18.3 bar