Magnum P62-Series Hardened Switches Installation and User Guide (05/05)
29
www GarrettCom com
.
.
connects to the PSX-T chassis. Ensure that each lead is securely tightened, then replace safety
shield. When power is applied, the green PWR LED will illuminate
NOTE (1):
Always use a voltmeter to measure the voltage of the incoming power supply
and figure out the +ve potential lead or -ve potential lead. The more +ve potential lead will
connect to the post labeled “+ve” and the rest to the “-ve”.
The GND can be hooked up at the last.
NOTE (2):
For best results at high-temperature, fasten the metal case of the PSX unit
to be in contact with a vertical surface (such as pedestal) that has good heat conducting
properties. Remove rubber “feet”, if present, to enhance metal-to-metal contact and provide the
best heat transfer away from the PSX unit.
UL Requirements
The following must be adhered to in order to conform to UL requirements:
6.
Minimum 18 AWG cable for connection to a Centralized DC power source.
7.
Minimum 14 AWG cable for connection to earthing wiring.
8.
Use only with Listed 10 A circuit breaker provided in building installation.
9.
“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or
equivalent.
10.
Fastening torque of the lugs on the terminal block: 9 inch pound max.
Centralized DC Power Source cable securement, use at least four cable ties to secure the
cable to the rack at least 4 inches apart with the first one located within 6 inches of the
terminal block.
3.4
Cable Strain Relief Feature on all P62-Series models
The Magnum P62-Series Hardened Switches are designed to use in extended
temperature environments, which qualifying them to be used in roadside traffic data collection
and control stations, above-the-ceiling locations in commercial buildings, etc. They are usually
mounted vertically so that the cables hang out the bottom. There is a cable strain relief feature
provided as part of the package
design
The Magnum P62-
Series Hardened Switches have
a tie wrap holder as part of the
base plate of the unit for cable
strain relief. The strain-relief
feature is applicable to power
cables as well as to Ethernet
cables, both twisted-pair copper
and fiber. Cable tie-wraps can
secure the cables and can be