Universal dimmer actuators GDA2K-400 KNX / GDA4K-400 KNX
pdated: Mai-17 (Subject to changes) Page 30 of 63
3.3.6 Soft switching
Table 12
Designation
Values
Description
Time for Soft ON
0 s, 1 s , 2 s, 4 s
6 s, , 8 s, 12 s, 15 s
24 s, 30 s, 45 s, 1 min
2 min, 3 min, 4 min, 5 min
6 min, 7 min, 8 min, 9 min
10 min, 12 min, 15 min, 20 min
30 min, 40 min, 50 min, 60 min
Duration of the dimming-up
phase (t1)
for Soft switching (see
appendix).
0 sec. = switch on immediately.
IMPORTANT
:
See appendix for further details:
Retriggering and premature
switch off
Dimming value after Soft ON
10%, 20%, 30%
40%, 50%, 60%,
70%, 80%, 90%, 100%
Final value at the end of the
Soft on phase (val)
Note:
Here again the configured
minimum dimming value needs
to be taken into account.
Time between Soft ON and Soft
OFF
until Soft OFF telegram
No time restriction; Soft Off
phase is initiated by a telegram.
1 s, 2 s, 3 s, 4 s
5 s, 6 s, 7 s, 8 s, 9 s
10 s, 15 s, 20 s, 30 s
40 s, 50 s, 1 min, 2 min
3 min, 4 min, 5 min, 6 min
7 min, 8 min, 9 min, 10 min
12 min, 15 min, 20 min, 30 min
40 min, 50 min, 60 min
Delay (t2) to the start of the Soft
Off phase
Time for Soft OFF
0 s, 1 s , 2 s, 4 s
6 s, , 8 s, 12 s, 15 s
24 s, 30 s, 45 s, 1 min
2 min, 3 min, 4 min, 5 min
6 min, 7 min, 8 min, 9 min
10 min, 12 min, 15 min, 20 min
30 min, 40 min, 50 min, 60 min
Duration of the Soft Off phase
(t3).
0 sec. = switch off immediately
IMPORTANT
:
See appendix for further details:
Retriggering and premature
switch off